2 multi turn encoder. qxm-1 thru 5, all rpms, 1 multi turn encoder removal – Flowserve QX Limitorque User Manual

Page 50

Advertising
background image

Limitorque QX Electronic Actuator FCD LMENIM3314-00 – 5/11

50

5.2 Multi Turn Encoder. QXM-1 thru 5, all RPMs

Table - 5.3 Multi-Turn Encoder Assembly

ITEM NUMBER

DESCRIPTION

(6.5 TURN)

DESCRIPTION

(20 TURN)

QTY.

(QX-1 &2)

QTY.

(QX-3 THRU 5)

17-1

DOWEL PIN

DOWEL PIN

1

1

17-2

6.5 TURN SPUR GEAR ASSY

SPUR GEAR ASSY

1

1

17-3

SOC HEAD CAP SCREW

SOC HEAD CAP SCREW

2

2

17-4

SPACER

SPACER

2

NA

17-5

SOCKET HEAD CAP SCREWS

SOCKET HEAD CAP SCREWS

2

2

17-6

SOCKET HEAD CAP SCREWS

SOCKET HEAD CAP SCREWS

3

3

Figure 5.4 - Multi-turn Encoder Assembly

5.2.1 Multi Turn Encoder Removal

Step 1

NOTE: The terminal block and power controls must be removed before removing the encoder. See section 6.4 for
terminal block and controls removal.

Disconnect the encoder ribbon cable connector from the Motor controller board, See section 6 for connector
placement. Using M3 Hex key remove the three screws (#17-6) that mount the encoder. Gently pull the encoder up and
out of the housing thru the terminal block bore.

Step 2

Using M3 Hex key (QX-1 & 2) or M2.5 Hex key (QX-3 thru 5) remove the two screws (#17-5) that mount the encoder
spur gear subassembly to the two housing pads.