Flowserve QX Limitorque User Manual

Page 65

Advertising
background image

65

Limitorque QX Electronic Actuator FCD LMENIM3314-00 – 5/11

flowserve.com

Installation with option boards:

1. Move JP1 jumper to the ‘NORM’ position

2. Insert PCB standoffs on populated side of board in holes marked ‘A’ as shown in Figure 6.13.

3. Mount board at end of board stack, plugging ribbon cable into the J2 receptacle on main board as shown

Figure 6.13 - Quik Power With Option Boards

Work on electronics if Quik Board is installed

1. Cycle through CHANGE SETTINGS menu until you reach CHANGE BACKUP POWER.

2. Select YES

3. Select BACKUP POWER DISABLED – OK?

4. Select YES

5. Exit CHANGE SETTINGS MENU

6. Turn power off to actuator, LCD and LEDS should still operate once power is removed. This is due to the quik board

still supplying power. Wait for unit to shut off.

7. Carefully remove electronics and Quik Board.

8. Locate JP1 (jumper) on JP1 of Quik Board and move to FAST DISCHARGE PINS.

Advertising