Automax Logix 3200IQ Digital Positioner

Installation, Operation and Maintenance Instructions

Figure 1: Logix 3200IQ Digital Positioner

Positioner Overview

The Logix 3200IQ digital positioner is a two-wire
4-20 mA input digital valve positioner. The positioner is
configurable through the local user interface. The Logix
3200IQ utilizes the HART protocol to allow two-way
remote communications with the positioner. The Logix
3200IQ positioner can control both double- and single-
acting actuators with linear or rotary mountings. The
positioner is completely powered by the 4-20 mA input
signal. Start up current must be at least 3.6 mA without
AO card or 3.85 mA with AO card.

Specifications

Table I: Electrical Specifications

Power Supply

Two-wire, 4-20 mA

10.0 to 30.0 VDC
Compliance Voltage

10.0 VDC @ 20 mA
495

Ω

@ 20 mA Typical

Effective Resistance

Add 20

Ω

when HART

communication active

Communications

HART Protocol

Minimum Operating

3.6 mA without AO board

Current

3.85 mA with AO board

Maximum Voltage

30.0 VDC

Table II: SoftTools Suite Software Specifications

Computer

Minimum Pentium processor running
Windows 95, 98, NT, 2000, XP, 32 MB
total memory (64 MB recommended),
30 MB available hard disk space,
CD-ROM drive

Ports

1 minimum available with 8 maximum
possible. (Can also communicate via

PCMCIA and USB connections)

HART Modem

RS-232/PCMCIA card/USB

HART Filter

May be required in conjunction with
some DCS hardware

HART MUX

MTL 4840/ELCON 2700

Table III: Environmental Conditions

Standard

-4° to 176°F

Operating Temperature

(-20° to 80°C)

Range

Low

-40° to 176°F
(-40° to 80°C)

Transport and Storage
Temperature Range

-40° to 176°F (-40° to 80°C)

Operating Humidity

0 to 100% non-condensing

Note: The air supply must conform to ISA Standard
ISA 7.0.01 (a dew point at least 18 degrees Fahrenheit
below ambient temperature, particle size below five
microns – one micron recommended – and oil content
not to exceed one part per million).

Table IV: Physical Specifications

Housing Material

Cast, powder-painted aluminum,
stainless steel

Soft Goods

Buna-N / Fluorosilicone

Weight

8.3 pounds (3.9 kg) aluminum
20.5 pounds (9.3 kg) stainless steel

Table V: Positioner Specifications

Deadband

<0.1% full scale

Repeatability

<0.05% full scale

Linearity

<0.5% (rotary), <0.8%,
(sliding stem) full scale

Air Consumption

<0.3 SCFM (0.5 Nm

3

/hr)

@ 60 psi (4 barg)