Automax logix 3200iq digital positioner – Flowserve Logix 3200IQ Digital Positioner User Manual

Page 3

Advertising
background image

Piezo Valve

Output 2

Output 1

Hall Effect
Sensor

Flame
Arrestor

Exhaust

Spool Valve

Flame
Arrestor

Pressure
Sensor Board

Air Supply

Analog Output Signal

Main PCB

Regulator

Filter

Flame
Arrestor

Digital Position Algorithm

LED
Display

HART
Terminals

Command
Input Signal

Air-to-Open

Configuration

Steam
Position
Sensor

Flowserve Corporation

1350 N. Mountain Springs Parkway

1978 Foreman Dr.

Flow Control Division

Springville, Utah 84663-3004

Cookville, TN 38501

www.flowserve.com

Phone: 801 489 2233

Phone: 931 432 4021

FCD AXAIM3200-00 9/04

Page: 3 of 32

© 2004, Flowserve Corporation, Printed in USA

Automax Logix 3200IQ Digital Positioner

Installation, Operation and Maintenance Instructions

Positioner Operation

The Logix 3200IQ positioner is an electric feedback
instrument. Figure 2 shows a Logix 3200IQ positioner
installed on a double-acting actuator.

The Logix 3200IQ receives power from the two-wire,
4-20 mA input signal. However, since this positioner
utilizes HART communications, two sources can be used
for the command signal: Analog and Digital. In Analog
source, the 4-20 mA signal is used for the command
source. In Digital source, the level of the input 4-20 mA
signal is ignored and a digital signal, sent via HART,
is used as the command source. The command source
selection can be accessed with SoftTools software, the
HART 275/375 communicator, or other host software.

The input signal in percent passes through a
characterization/limits modifier block. The positioner
no longer uses CAMs or other mechanical means to
characterize the output of the positioner. This function
is done in software, which allows for in-the-field
customer adjustment. The positioner has three basic
modes: Linear, Equal Percent (=%) and Custom
characterization. In Linear mode, the input signal is
passed straight through to the control algorithm in a
1:1 transfer. In Equal Percent (=%) mode, the input signal
is mapped to a standard 30:1 rangeability =% curve.
If Custom characterization is enabled, the input signal
is mapped to either a default =% output curve or a
custom, user-defined 21-point output curve. The custom

Figure 2: Logix 3200IQ Digital Positioner Schematic (air-to-open configuration)

Table VI: 4 to 20 mA Analog Output Specifications

Potential Range

40° to 95°

of Rotation
Power Supply Range

12.5 to 40 VDC, (24 VDC typical)

Maximum Load

(Supply voltage - 12.5) / 0.02

Resistance (ohms)
Current Signal Output

4-20 mA

Linearity

1.0% F.S.

Repeatability

0.25% F.S.

Hysteresis

1.0% F.S.

Operating Temperature -40° to 176°F, -40° to 80°C

Table VII: Hazardous Area Certifications

FM/CSA
Intrinsically Safe

Explosion Proof

Class I, Div 1, Groups A, B, C, D

Class I, Div 1,
Groups A, B, C, D

Class II, Div 1, Groups E, F, G

Class II, Div 1,
Groups E, F, G

(See Figure 2 for installation requirements.)
CENELEC

II 1G EEx ia IIC T4, T5

Intrinsically Safe

T4 Ta = -40°C to 80°C
T5 Ta = -40°C to 35°C

Flameproof

II 2 GD EEx d IIB + H

2

T5, Ta = -40°C to 80°C

Compliant