Fronius Selectiva 8 kW User Manual

Page 29

Advertising
background image

27

EN

-

Error overtemperature ON/OFF:
-

ON ... Error message in the event of battery overtemperature
Charging process stops and can only be continued once the battery has cooled
down and been reconnected

-

OFF ... No error message in the event of battery overtemperature

-

Warning overtemperature ON/OFF:
-

ON ... Warning in the event of battery overtemperature

-

OFF ... No battery overtemperature warning

Equalize charge:
-

ON:
If the battery remains connected to the battery charging system for the duration of the
"equalize charge delay", then a special type of charging takes place. This prevents
acid stratification.

-

OFF:
There is no equalising charge.

Delay:

Charge start delay:
Delay time (minutes) of actual start of charging relative to the moment when charge start
was initiated

Charge end delay:
Delay time (minutes) before charge end is signalled (e.g. green indicator) relative to the
moment when charging actually stopped

At mains failure restart charging:
If this option is chosen, the charging process is restarted automatically as soon as the
mains supply becomes available again after a disruption to the electrical mains supply.

Calendar:

The calendar function allows charging to be started automatically according to the follow-
ing criteria:
-

Time window in which charging may not be started if a battery is connected

-

Time window in which charging is to be started using a defined characteristic 1 if a bat-
tery is connected

-

Time window in which charging is to be started using a defined characteristic 2 if a bat-
tery is connected

To activate the calendar function,
select the setting "ON" and confirm

Definition of characteristic 1:
-

Type of battery
e.g. Pb-Wet

-

Characteristic:
e.g. RI

-

Additional settings, depending on the
characteristic:
e.g. Charging time 7-8 h