4 activate set-up mode – ifm electronic RN3001 User Manual

Page 16

Advertising
background image

Encoder with Profibus interface

16

Resolution per physical measuring steps

The requested number of steps refers to the data entered via the [Physical

impulses] parameter (→ chapter 10.1.7).

This is the numerical value that is read from the coded disc inside the encoder

(e�g� 4096 steps per revolution for the standard 12-bit version)�

This option allows free setting of gearbox factors�

Reference

Octet 26 bit 0

Octet 26 bit 1

Per revolution

0

0

Per max� total resolution

1

0

Per physical measuring steps
(= steps indicated in octets 35-38)

0

1

10.1.4 Activate set-up mode
Bit 2 in octet 26 is a switch for the set-up mode�
In this mode other parameters besides the preset value can be transferred to the

encoder�
With activated mode a teach operation can be carried out; the gearbox factor can

be directly determined in the system�
In this mode (green LED flashing) the direction of rotation and scaling set during

projection are ignored and the values saved in the internal EEPROM are used�
The device can be operated permanently in the set-up mode�
Recommendation:

Transfer the parameters determined in the set-up mode and then use the device in

normal mode (which enables a replacement of the device without having to repeat

the teach operation)�

Octet 26 bit 2

Set-up mode

0

Off

1

On