Encoder with Profibus interface

26

11.2.6 Number of revolutions
The physical number of the distinguishable revolutions per encoder can be

enquired via the two diagnostic bytes 15 and 16� The standard values for

singleturn is 1 and 4096 (or 16384) for multiturn�
11.2.7 Operating time alarm
The warning message for exceeding the operating time is indicated in bit 4 of

diagnostic byte 21� The bit is set after 10

5

hours�

11.2.8 Profile version
The profile version of the encoder is stored in the diagnostic bytes 24 and 25�

Bytes

24

25

Bit

15���8

7���0

Data

2

7

���2

0

2

7

���2

0

Revision no�

Index

11.2.9 Software version
The software version of the encoder is stored in the diagnostic bytes 26 and 27�

Octet

26

27

Bit

15���8

7���0

Data

2

7

���2

0

2

7

���2

0

Revision no�

Index

11.2.10 Operating time
The operating time of the device is recorded in the diagnostic bytes 28���31� While

the supply voltage is applied, the value (Operating time) is stored again in the

encoder in steps of 0�1 every 6 minutes�
11.2.11 Zero point shift
The zero point shift is provided in the diagnostic bytes 32���35�
11.2.12 Configured resolution
The configured resolution per revolution of the encoder is stored in the diagnostic

bytes 40���43� This value is only valid if the gearbox factor was calculated in the

parameter mask via the setting [Resolution per revolution]�
11.2.13 Configured total resolution
The configured or calculated total resolution is stored in diagnostic bytes 44���47�