Nortec Modbus User Manual

Page 16

Advertising
background image

SP_Chan_B

1

Writes the

desired space

setpoint for

control channel 1

for cylinder B

40008

Holding

Register Integer

0 - 95

%

Write

Use only with NH-EL-

150 and NH-EL-200

models when sending

RH value to Dinput_B1

and cylinders are in

independent operation

mode

SP_Chan_B

2

Writes the

desired space

setpoint for

control channel 2

for cylinder B

40009

Holding

Register Integer

10 - 95

%

Write

Use only with NH-EL-

150 and NH-EL-200

models when sending

RH value to Dinput_B2

with dual channel

control enabled and

cylinders are in

independent operation

mode

Signal_

Source

Selects signal

source to control

unit

40014

Holding

Register Integer

0 - 4

-

Write

0 = Analog

1 = Modbus

2 = BACnet/IP

3 = BACnet/MS

4 = LonWorks

Control_

Mode

Selects method

to control unit

40015

Holding

Register Integer

1 - 3

-

Write

1 = Demand

2 = RH P

3 = RH PI

Control_

Channel

Selects method

to control

channels

40016

Holding

Register Integer

0 - 1

-

Write

0 = Single Channel

1 = Dual Channel

Input_A1

Displays channel

1 demand for

cylinder A

30004

Input

Register Integer

0 - 100

%

Read

Displays channel 1

demand/sensed RH as

a percentage of cylinder

capacity for cylinder A

Input_A2

Displays channel

2 demand for

cylinder A

30005

Input

Register Integer

0 - 100

%

Read

Displays channel 2

demand/sensed RH as

a percentage of cylinder

capacity for cylinder A

Input_B1

Displays channel

1 demand for

cylinder B

30014

Input

Register Integer

0 - 100

%

Read

Displays channel 1

demand/sensed RH as

a percentage of cylinder

capacity for cylinder B

(NH-EL-150 and NH-EL-

200 models only)

Input_B2

Displays channel

2 demand for

cylinder B

30015

Input

Register Integer

0 - 100

%

Read

Displays channel 2

demand/sensed RH as

a percentage of cylinder

capacity for cylinder B

(NH-EL-150 and NH-EL-

200 models only)

Blower_

Pack_A

Reads the status

of the blower

pack for cylinder

A

30008

Input

Register Integer

0 or 1

-

Read

0 = Open

1 = Closed

Blower_

Pack_B

Reads the status

of the blower

pack for cylinder

B

30018

Input

Register Integer

0 or 1

-

Read

0 = Open

1 = Closed

Fan_

Activate_A

Indicates if air

handle or

furnace is

activated for

cylinder A

30009

Input

Register Integer

0 or 1

-

Read

0 = Not Activated

1 = Activated