Nortec Modbus User Manual

Page 40

Advertising
background image

Status

Displays

status of

various

components

.

30107 Input

Register Integer 0 - 128 -

Read

Significant bits: 1 (Bit

0), 2 (Bit 1), 4 (Bit 2), 8

(Bit 3), 16 (Bit 4), 32

(Bit 5), 64 (Bit 6), 128

(Bit 7).

Bit 0 = Contactor

Bit 1 = Fill Valve

Bit 2 = Drain Valve

Bit 3 = Blower pack fan

Bit 4 = Collective fault

(see 30108 for details)

Bit 5 = Humidifier Active

A “1” in the appropriate

bit location indicates

that the component is

active.

MaxOutput

Displays the

maximum

capacity of

humidifier.

30111 Input

Register Integer 0 - 30

lbs/hr

Read

The maximum amount

of steam per hour that

the humidifier can

produce in lbs/hr. This

value is copied from

Model (40205).

Modulation

Displays the

value of

modulating

signal when

a local

modulating

humidistat

is used.

30102 Input

Register Integer

0-

1023

-

Read

Values are displayed as

whole numbers with 2

decimals places.

Example:

1023 = 10.23 volts

500 = 5.00 volts

A constant value of

1023 can indicate the

jumper J10 is installed.

FaultCode

Indicates

the

presence of

a fault and

which fault

has been

detected.

30108 Input

Register Integer

0-

32768 -

Read

0 = (Amber LED 1 flash)

Excess current.

1 = (Amber LED 3 flash)

High water level, no

current.

2 = (Amber LED 2 flash)

No current detected

3 = (Amber LED 4 flash)

End of cylinder life.

CtrlStatus1

Describes

controller

hardware

and jumper

statuses.

30109 Input

Register Integer

0-

32768 -

Read

Uses significant bits 0

through 15 (1, 2, 4, 8,

16, 32, 64, 128, 256,

512, 1024, 2048,

4096, 8192, 16384,

32768 respectively).

Bit 1 - Electrodes

passing current (0 = On)

Bit 2 - FAULT Relay (0 =

On)

Bit 3 - YELLOW LED

(1 = Illuminated)

Bit 4 - GREEN LED

(0 = Illuminated)

Bit 5 - FAN (1 = On)

Bit 8 - High Water Input

(0 = High Water)

Modbus Installation | 37

Advertising