Mhtc evaporative media humidifiers, Modbus address – Nortec Modbus User Manual

Page 32

Advertising
background image

MHTC Evaporative Media Humidifiers

After wiring connections have been completed, the humidifier needs to be setup to operate and

communicate through the Modbus interface.

Modbus Address

The default Modbus address for a MHTC is 1. If multiple units were included on an order, the

addresses of individual units may vary.

To view or change the unit number:

1 Press the Menu key to access the menu.
2 Select the User option and press Set.
3 When prompted for a password, enter 8808 using the arrow keys. Press Set to confirm.
4 Select the Settings menu and press the Set key.
5 Select the Modbus menu and press the Set key.
6 Select the Address setting and press Set to modify. Enter a value between 1 and 127

inclusive as desired and press Set to confirm the solution. It is recommended to leave the
parity and timeout settings to their factory defaults (None1 and 300 respectively) unless
communication problems occur.

7 Press Esc repeatedly until you return to the home screen.

This procedure is summarized below:

Menu > User > 8808 > Modbus >

Parity: None1

Addr: 1 (Default, 1 – 127 acceptable)

Timeout: 300 seconds (Default, 5 – 600 acceptable)

Modbus Installation | 29