The following points may be mapped for control:

Variable

Name

Description

Addr

Type

Format Range Unit R/W

Additional Details

RHDem1

Write RH or

Demand signal

value to control

channel 1

40264 Holding

Register Analog

0-100

%

Write Requires network controls

(NetSensor = 1)

RhDem2

Write RH or

Demand signal

value to control

channel 2

40265 Holding

Register Analog

0-100

%

Write Requires network controls

(NetSensor = 1)

Set1

Writes the desired

space setpoint for

control channel 1

40024 Holding

Register Analog

30-95

%

Write Use only when sending RH

value to RHDem1

Set2

Writes the desired

space setpoint for

control channel 2

40025 Holding

Register Analog

30-95

%

Write Use only when sending RH

value to RHDem2

Disable

Remotely disables

the humidifier

40262 Holding

Register Analog 0, 255

-

Write 0 = Run

255 = Disable

InputType

Selects the control

type that the

humidifier

operates on

40007 Holding

Register Analog 0,1,2,3

-

Write

0 = Demand Signal

1 = On/Off Signal

2 = RH Sensor Value (Use

Proportional Control)

3 = RH Sensor Value (Use

Proportional-Integral

Control)

NetSensor

Switches between

hard wired or

network control

signal

40226 Holding

Register

Binary

0,1

-

Write

0 = Hard wired control

signal

1 = Use Modbus to write

control signal value

RHDem1

Read RH or

Demand signal

value from control

Channel 1

30348

Input

Register Analog

0-100

%

Read Displays signal value as a

percentage

RHDem2

Read RH or

Demand signal

value from control

Channel 2

30349

Input

Register Analog

0-100

%

Read Displays signal value as a

percentage

Set1

Read space

setpoint for control

channel 1

40024

Input

Register Analog

30-95

%

Read Only available for InputType

2 or 3

Set2

Read space

setpoint for control

channel 2

40025

Input

Register Analog

30-95

%

Read Only available for InputType

2 or 3

Disable

Confirms remote

disable status

30989

Input

Register Analog 0, 255

-

Read 0 = Run

255 = Disable

InputType

Confirms the

control type that

the humidifier

operates on

40007

Input

Register Analog 0,1,2,3

-

Read

0 = Demand Signal

1 = On/Off Signal

2 = RH Sensor Value (Use

Proportional Control)

3 = RH Sensor Value (Use

Proportional-Integral

Control)

Modbus Installation | 27