Control signal setting – Nortec Modbus User Manual

Page 33

Advertising
background image

Control Signal Setting

By default the humidifier is configured operate on a hardwired control signal supplied through

the unit terminal strip. This can be changed to allow the humidifier to function entirely through

its Modbus interface.

To adjust this setting:

1 Press the Menu key to access the menu.
2 Select the User options and press Set.
3 When prompted for a password, enter 8808 using the arrow keys. Confirm the password

with set.

4 Select the Controls menu and press the Set key. The following settings can be adjusted:

Signal Source

Analog: Use hardwired control signal

Modbus: Write control signal through Modbus interface

Hum. Control

External: Use a demand control signal

Int(p): Use a sensor value and proportional

int(pi): Use a sensor value and proportional-integral control band

Control Sign

Setting not relevant when writing control signal through Modbus.

Note: Refer to the

MHTC Humidifier Configuration

section of the MH Series Installation and

Operation Manual for more information on the above settings.

1 Press Esc repeatedly to return to the home screen when complete.

This procedure is summarized below:

Menu > User > 8808 > Controls >

Signal Source: Analog or Modbus

Hum. Control: External, Int(p), or Int(pi)

Control Sign: As required

30

|Modbus Installation