Control signal setting – Nortec Modbus User Manual

Page 19

Advertising
background image

Control Signal Setting

By default the humidifier operation is configured on a hardwired control signal supplied through

the unit terminal strip. This can be changed to allow the humidifier to function entirely through

its Modbus interface.

To adjust this setting:

1 Press the Menu key to access the menu.
2 When prompted for a password, enter 0335 using the arrow keys. Confirm the password

with set.

3 Select the Control Settings menu and press the Set key. The following settings can be

adjusted:

Source

Analog: Use hardwired control signal

Digital: Write control signal through Modbus interface

REG Mode

Demand: Use a demand control signal

RHp: Use a sensor value and proportional

RHpi: Use a sensor value and proportional-integral control band

MOD Mode

Single CH: Use a signal channel control signal

Dual CH: Use a dual channel control signal

CNT Type

Setting not relevant when writing control signal through Modbus.

Note: Refer to the CONTROL SETTING section of the NH Series Installation and Operation
Manual for more information on the above settings.

4 Press Esc repeatedly to return to the home screen when complete.

This procedure is summarized below:

Menu > 0335 > Control Settings >

Source: Analog or Digital

Reg Mode: Demand, RHp, or RHpi

Mod Mode: Single CH or Dual CH

CNT Type: As required

16

|Modbus Installation