Nortec Modbus User Manual

Page 26

Advertising
background image

The following points may be mapped for control:

Variable

Name

Description

Addr

Type

Format Range

Unit

R/W

Additional Details

RHDem1

Write RH or

Demand signal

value to control

channel 1

40264 Holding

Register

Analog

0-100

%

Write

Requires network

controls

(NetSensor = 1)

RhDem2

Write RH or

Demand signal

value to control

channel 2

40265 Holding

Register

Analog

0-100

%

Write

Requires network

controls

(NetSensor = 1)

Set1

Writes the

desired space

setpoint for

control channel 1

40024 Holding

Register

Analog

30-95

%

Write

Use only when

sending RH value

to RHDem1

Set2

Writes the

desired space

setpoint for

control channel 2

40025 Holding

Register

Analog

30-95

%

Write

Use only when

sending RH value

to RHDem2

Disable

Remotely

disables the

humidifier

40262 Holding

Register

Analog

0, 255

-

Write 0 = Run

255 = Disable

InputType

Selects the

control type that

the humidifier

operates on

40007 Holding

Register

Analog 0,1,2,3

,

-

Write

0 = Demand Signal

1 = On/Off Signal

2 = RH Sensor

Value (Use

Proportional

Control)

3 = RH Sensor

Value (Use

Proportional-

Integral Control)

NetSensor

Switches

between hard

wired or network

control signal

40226 Holding

Register

Binary

0,1

-

Write

0 = Hard wired

control signal

1 = Use Modbus to

write control signal

value

RHDem1

Read RH or

Demand signal

value from

control Channel

1

30348

Input

Register

Analog

0-100

%

Read

Displays signal

value as a

percentage

RHDem2

Read RH or

Demand signal

value from

control Channel

2

30349

Input

Register

Analog

0-100

%

Read

Displays signal

value as a

percentage

Set1

Read space

setpoint for

control channel 1

40024

Input

Register

Analog

30-95

%

Read Only available for

InputType 2 or 3

Set2

Read space

setpoint for

control channel 2

40025

Input

Register

Analog

30-95

%

Read Only available for

InputType 2 or 3

Disable

Confirms remote

disable status

30989

Input

Register

Analog

0, 255

-

Read 0 = Run

255 = Disable

Modbus Installation | 23