NetSensor

Confirms the

system control

type

40226

Input

Register Binary

0,1

-

Read

0 = Hard wired control

signal

1 = Use Modbus to write

control signal value

Fault

Read fault status

30301

Input

Register Binary

0,1

-

Read 0 = No Fault

1 = Fault Detected

Service

Read service

warning status

30300

Input

Register Binary

0,1

-

Read 0 = No Service Warning

1 = Service Required

Status

Read

humidification

status

30302

Input

Register Binary

0,1

-

Read 0 = Idle / Standby

1 = Active / Humidifying

Connection

Read connection

status

40267

Input

Register Binary

0,1

-

Read

0 = Communication Error

1 = Normal

Communication

HourOpt

Read operational

hours of unit

30350

Input

Register Analog

0 -

Infinity hrs Read

Displays hours of

operation.

KeepWarm

Read keepwarm

option status

(enable/disable at

humidifier)

30356

Input

Register Analog

0,1

-

Read

Bit0 - KEEPWARM

0 = Disabled

1 = Enabled

3DayDrain

Read 3 day drain

option status

(enable/disable at

humidifier)

30356

Input

Register Analog

0,1

-

Read

Bit1 - 3 DAY DRAIN

0 = Disabled

1 = Enabled

SysDemand Read system

output / demand

30347

Input

Register Analog

0-100

%

Read Displays output as

percentage of capacity

ServHours

Read hours before

next service

30352

Input

Register Analog

500-0

hrs Read Displays hours remaining

until next service.

SecurityLoop

Displays status of

security loop.

30364

Input

Register Analog

0,1

-

Read

Displays the status of the

security loop on terminals

1 and 2. Loop must be

"closed" for humidifier to

operate.

0 = Open

1 = Closed