Nortec Modbus User Manual

Page 23

Advertising
background image

Cyl2OpTime

Reads

operating

time for

cylinder 2

31213

Input

Register Integer

0 -

6553

5

5

min

Read

Reads operating time

for cylinder 2 (NHTC-

150 and NHTC-200

only). Each number is

equivalent to 5 minutes

of operation.

Time in hours = (Value x

5)/60

UnitStatus

Displays

status

warnings

31385

Input

Register Integer 0-99

-

Read

11 = Security loop open

19 = Cylinder spent

warning

If status 19, unit will

have yellow service light

on and will continue to

run for 72hrs

CylSpent

Displays

cylinder end

of life fault

30378

Input

Register Integer 0-99

-

Read

Unit will not run until

cylinder is replaced

19 = Cylinder spend

fault

SysTotalDem

Displays the

total demand

on system

(sum both

cylinders)

30251

Input

Register Integer

0 -

100

%

Read

Sum of Steam Output

Cyl-1 and Cyl-2 in

percentage

20

|Modbus Installation