4 water installation, 1 notes on water installation, Water installation – Nortec ME Control Installation User Manual

Page 27: Notes on water installation

Advertising
background image

27

Installation

4.4

Water installation

4.4.1 Notes on water installation

The layout of the water piping (distribution, supply and drain water piping) depends on the system version.

Refer to the corresponding chapter for detailed information and observe the following installation notes.

Notes on distribution piping
– The distribution piping is to be carried out according to the figures found in chapter 4.4.4 – Mount-

ing the control unit and 4.4.3 – Water installation (external installation) and the applicable local

regulations for water installations. The indicated connection specifications and connection layout

must be observed.

– The distribution piping is made of ø15 mm (0.625") black plastic hoses (supplied as part of the

internal installation kit) or stainless steel pipe (supplied as part of the external installation kit).

– Make sure the distribution hoses have a constant downslope (no sagging) to the hydraulic module

and are not kinked over the entire length.

– All connections are made with push-fit fittings.
– On systems where the hydraulic module is mounted outside the duct, the supplied feed throughs

and hose supports must be used.

General notes on installation of the hoses
– Use the supplied black plastic hoses ø15 mm (0.625") only. For hygienic reasons do not use

other hoses (except products supplied by your Nortec distributor).

– When cutting hoses use an

appropriate cutting tool providing straight, kink-free cuts.

CAUTION!

After cutting the hoses any

sharp edges must be deburred otherwise the couplings may be

damaged.

– The hoses must be free of kinks and other damage (longitudinal scratches or misshaped ends,

in particular).

– When cutting hoses always

add at least 5 to 10 mm (0.2" to 0.4") to the required length. This

way the hoses can be fastened correctly (down to the stop) to the push-fit couplings.

– Make sure the hoses are not kinked and pay attention to the

mini mum bend radius of 100 mm (4").

– Do not lead hoses past hot system components (

max. ambient temperature is 40 °C/104 °F).

– After installation verify correct fastening of all hoses. Correctly mount ed hoses can not be re-

moved without pressing the locking ring.

CAUTION!

In order to avoid damage caused by leaking water during operation, all hoses must correctly be

secured against accidently pulling out.

Advertising