4.4.4

Mounting the control unit

4.4.5 Notes on positioning the control unit

Please observe the following notes when positioning the Nortec ME control unit:
– The control unit can be mounted directly outside to the AHU/air duct or to a wall or stand (not sup-

plied).

– The control unit should ideally be positioned as close to the evaporative module as possible for ease

of servicing and maintenance.

Note: the hydraulic module of Nortec ME Controls is equipped with a 5 m (16.4’) 14-core electrical

inter-connecting cable for connection to the control unit. Make sure the control unit is mounted within

the range of the inter-connecting cable.

– The control unit is protected according to

IP21. Make sure the control unit is installed in a drip-proof

location and the admissible ambient conditions are complied with (see technical data in the opera-

tion manual to the Nortec ME Control).

– The power supply to the control unit must be equipped with an electrical isolator (not supplied) fitted

within 1 m (39") for purposes of maintenance and emergencies. When positioning the control unit

make sure the electrical isolator can be mounted within that range.