30 Installation

4.4.3 Water installation (external installation)

Stages

(box rows)

Connection layout

distribution hoses

2

2 1

4 2 1 3 5

3

2 1 3

4 2 1 3 5

4

4 2 1 3

4 2 1 3 5

5

4 2 1 3 5

4 2 1 3 5

Distribution hoses

ø15 mm (0.625")

constant slope

(no sagging)

Water supply push-fit

connector ø15 mm (0.625")

Feed through

(supplied)

Drain pipe ø28 mm (1.125")

with constant downslope

1...2 % (not supplied)

Shut-off valve

(supplied)

Drain trap (not supplied)

Drain trap height: Allow a height of 25 mm

(1") for every 250 Pa of duct pressure (e.g.

100 mm (4") for 1000 Pa duct pressure)

Pressure equalisation pipe

(mandatory, not supplied)

Open tundish (not supplied)

Important: the drain pipes must not touch the

tundish - allow air gap of min 20 mm (0.8" ).

AHU drain with drain trap (not supplied)

Drain trap height: Allow a height of 25 mm

(1") for every 250 Pa of duct pressure (e.g.

100 mm (4") for 1000 Pa duct pressure).

2...5 bar

Fig. 18: Water installation (external installation)

Drain pipe vent (mandatory,

not supplied), highest point

of vent tube must be above

max. water level of tank