3 installation work, Installation work – Nortec ME Control Installation User Manual

Page 37

Advertising
background image

37

Installation

4.5.3 Installation work

Note: for the connection of the available options please refer to the installation and operation manual

of the corresponding option.

Control signal (Y)
Note: the control settings must be done via the control software of the Nortec ME Control. Please

refer to the operation manual of the Nortec ME Control.

X16

JP5: 10V JP4: 24V

B7

24 V

TMP

GND

HUM

24V E

Enable

P/PI

24 V

rh

24 V - voltage supply

Control unit

External continuous humidity or temperature con-

troller
An external continuous humidity or temperature controller

is to be connected to the contacts “HUM” (+) and “GND”

(–) of the terminal block “X16” on the driver board in ac-

cordance with the wiring diagram. The admissible signal

values can be found in the technical data table in the

operation manual. The connecting cable must either be

fed through the rectangular cable feed through or a free

cable gland into the control unit.

Note: If 24V supply is used for the external controller

Jumper “JP4: 24V” must be set and Jumper “JP5: 10V”

must be removed.

The shielding of the control signal must be connected

to terminal “GND”.

Caution! If the shielding of the control signal is already

connected to a po ten tial or a grounded conductor,

do not connect it to terminal “GND”.

X16

JP5: 10V JP4: 24V

Y

B7

HUM

24/10V

TMP

GND

HUM

24V E

Enable

24 V

rh

24 V - voltage supply

Control unit

Humidity sensor
A humidity sensor is to be connected to the contacts

“HUM” (+) and “GND” (–) of the terminal block “X16” on

the driver board. The admissible signal values can be

found in the technical data table in the operation manual.

The connecting cable must either be fed through the

rectangular cable feed through or a free cable gland

into the control unit.

Note: If 24V supply is used for the external controller

Jumper “JP4: 24V” must be set and Jumper “JP5: 10V”

must be removed.

The shielding of the control signal must be connected

to terminal “GND”.

Caution! If the shielding of the control signal is already

connected to a po ten tial or a grounded conductor,

do not connect it to terminal “GND”.

Advertising