Data arrays, Pt-link-lon, Technical guide – Orion System PT-Link-LON User Manual

Page 14: Pt-link interface 14

Advertising
background image

PT-Link-LON

®

Technical Guide

PT-Link Interface

14

Data Arrays

Table 3: VCM-X WSHP (Tulsa) Data Array For Field Server

Table 2: VCM-X Modular Data Array For Field Server

VCM-X Modular Data Array For Field Server

Offset

0

1

2

3

4

5

6

7

0

AppVer

ClSt

HtSt

OaWtbl

TpDmnd

SpcTp

SaTp

RaTp

8

OaTp

DuctPr

OaRh

UnitMode

CtrlSts

ClEnbl

HtEnbl

EcoEnbl

16

FanDly

PofCfg

CO2Cfg

MdHt2Ins

Rt2Ins

OnRlys

ExRlys12

ExRlys34

24

EcoPos

VfdBwPos

VfdExPos

AlrmSts

AlrmGrp1

AlrmGrp2

AlrmGrp3

SaTpAlm

32

OaTpAlm

SpcTpAlm

MchClAlm

MchHtAlm

PofAlm

DrtFAlm

SmokeAlm

LoSaAlm

40

HiSaAlm

CtrlTpCF

CtrlTpHF

CtrlTp

InRh

InRhStM

DptStM

MdClPos

48

MdHtPos

MdHt2Pos

Rt2Pos

OcpClSt

OcpHtSt

UnClOst

UnHtOst

WtblSt

56

SaClSt

SaHtSt

WmupSt

SpcTpOst

SaTpOst

RaTpOst

OaTpOst

CoilTpSt

64

DptSt

InRhSt

DuctPrSt

RfPrSt

SchdFrc

OnRly1

OnRly2

OnRly3

72

OnRly4

OnRly5

ExRly1

ExRly2

ExRly3

ExRly4

ExRly5

ExRly6

80

ExRly7

ExRly8

ExRly9

ExRly10

ExRly11

ExRly12

ExRly13

ExRly14

88

ExRly15

ExRly16

CO2St

MinEcoSt

CO2Level

ByPasDmp

RaDmp

RfPr

96

OaDwpt

CoilTp

SaTpStM

PreHtSp

OaCFM

EtCFM

SaCFM

OACfmSt

104

OACfmRs

OACfmStM

MdCmp2

HdPr1

HdPr2

CdFan1

CdFan2

VCM-X WSHP (Tulsa) Data Array For Field Server

Offset

0

1

2

3

4

5

6

7

0

AppVer

ClSt

HtSt

OaWtbl

TpDmnd

SpcTp

SaTp

RaTp

8

OaTp

DuctPr

OaRh

UnitMode

CtrlSts

ClEnbl

HtEnbl

EcoEnbl

16

FanDly

PofCfg

CO2Cfg

MdHt2Ins

Rt2Ins

OnRlys

ExRlys12

ExRlys34

24

EcoPos

VfdBwPos

VfdExPos

AlrmSts

AlrmGrp1

AlrmGrp2

AlrmGrp3

SaTpAlm

32

OaTpAlm

SpcTpAlm

MchClAlm

MchHtAlm

PofAlm

DrtFAlm

SmokeAlm

LoSaAlm

40

HiSaAlm

CtrlTpCF

CtrlTpHF

CtrlTp

InRh

InRhStM

DptStM

MdClPos

48

MdHtPos

MdHt2Pos

Rt2Pos

OcpClSt

OcpHtSt

UnClOst

UnHtOst

WtblSt

56

SaClSt

SaHtSt

WmupSt

SpcTpOst

SaTpOst

RaTpOst

OaTpOst

CoilTpSt

64

DptSt

InRhSt

DuctPrSt

RfPrSt

SchdFrc

OnRly1

OnRly2

OnRly3

72

OnRly4

OnRly5

ExRly1

ExRly2

ExRly3

ExRly4

ExRly5

ExRly6

80

ExRly7

ExRly8

ExRly9

ExRly10

ExRly11

ExRly12

ExRly13

ExRly14

88

ExRly15

ExRly16

CO2St

MinEcoSt

CO2Level

ByPasDmp

RaDmp

RfPr

96

OaDwpt

CoilTp

SaTpStM

PreHtSp

OaCFM

EtCFM

SaCFM

OACfmSt

104

OACfmRs

OACfmStM

MdCmp2

HdPr1

HdPr2

CdFan1

CdFan2

WaterTpA

112

WaterTpB

A1LSPAlm

A1LktAlm

A2LSPAlm

A2LktAlm

B1LSPAlm

B1LktAlm

B2LSPAlm

120

B2LktAlm

LWT1Alm

LWT2Alm

POWF1Alm

POWF2Alm

ComMAlm

Advertising