Appendix e - sa controller lon parameters, Pt-link-lon, Technical guide – Orion System PT-Link-LON User Manual

Page 30: Pt-link interface 30, Sa controller pt-link-lon, Property identifi er

Advertising
background image

PT-Link-LON

®

Technical Guide

PT-Link Interface

30

Appendix E - SA Controller LON Parameters

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Expansion

Relay 8

ExRly8

Binary
Output

Current status of relay 13.

Expansion

Relay 9

ExRly9

Binary
Output

Current status of relay 14.

Expansion

Relay 10

ExRly10

Binary
Output

Current status of relay 15.

Expansion

Relay 11

ExRly11

Binary
Output

Current status of relay 16.

Expansion

Relay 12

ExRly12

Binary
Output

Current status of relay 17.

Expansion

Relay 13

ExRly13

Binary
Output

Current status of relay 18.

Expansion

Relay 14

ExRly14

Binary
Output

Current status of relay 19.

Expansion

Relay 15

ExRly15

Binary
Output

Current status of relay 20.

Expansion

Relay 16

ExRly16

Binary
Output

Current status of relay 21.

Emergency

Shutdown

Alarm

EmerAlm

Binary
Output

Alarm that indicates

Emergency Shutdown.

Drain Pan

Overfl ow

DrnAlm

Binary
Output

Alarm that indicates overfl ow of

the drain pan.

Proof of

Water Flow

Alarm

PoWFAlm

Binary
Output

Alarm that indicates no

Proof of Water Flow.

Entering Air
Temperature

Alarm

EaTpAlm

Binary
Output

Alarm that indicates

failure in the Entering Air

Temperature Sensor.

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Dirty Filter

Detected

DrtFlAlm

Binary
Output

Alarm that indicates

the fi lters are dirty.

Control

Temperature
Cool Failure

CtrlTpCF

Binary
Output

This alarm is activated if the
control temperature does not

get within 5°F to the occupied

cooling setpoint in an hour in the

cooling mode. This alarm is not

used in 100% outside air units or

supply air control.

Control

Temperature

Heat Failure

CtrlTpHF

Binary
Output

This alarm is activated if the
control temperature does not

get within 5°F to the occupied

heating setpoint in an hour in the

heating mode. This alarm is not

used in 100% outside air units or

supply air control.

Space

Temperature

Sensor Lost

SpcTpAlm

Binary
Output

Alarm that indicates a failure in

the space temperature sensor.

On Board

Relay 1

OnRly1

Binary
Output

Current status of relay 1.

On Board

Relay 2

OnRly2

Binary
Output

Current status of relay 2.

On Board

Relay 3

OnRly3

Binary
Output

Current status of relay 3.

On Board

Relay 4

OnRly4

Binary
Output

Current status of relay 4.

On Board

Relay 5

OnRly5

Binary
Output

Current status of relay 5.

Expansion

Relay 1

ExRly1

Binary
Output

Current status of relay 6.

Expansion

Relay 2

ExRly2

Binary
Output

Current status of relay 7.

Expansion

Relay 3

ExRly3

Binary
Output

Current status of relay 8.

Expansion

Relay 4

ExRly4

Binary
Output

Current status of relay 9.

Expansion

Relay 5

ExRly5

Binary
Output

Current status of relay 10.

Expansion

Relay 6

ExRly6

Binary
Output

Current status of relay 11.

Expansion

Relay 7

ExRly7

Binary
Output

Current status of relay 12.

SA Controller PT-Link-LON

®

Property Identifi er:

The PT-Link-LON

®

Link amends the following property identity to the

BACnet

®

property identifi er.

LONPropertyIdentifi er :

VcmxControlStatusBits ::= ENUMERATED {

Off

(0),

Vent

(1),

Cool

(2),

Heat

(3),

Dehum

(4),

Dehum

Cool

(5),

Dehum

Heat

(6),

Warm

Up

Mode

(7)

}