Appendix d - vcm-x lon parameters, Pt-link interface, Pt-link-lon – Orion System PT-Link-LON User Manual

Page 23: Technical guide 23

Advertising
background image

PT-Link Interface

PT-Link-LON

®

Technical Guide

23

Appendix D - VCM-X LON Parameters

SNVTs for the VCM-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Warm Up

Setpoint

WmupSt

Analog

Input

In a VAV

application, upon

entering the

occupied mode,

the Warm-up

Demand will be

activated if the

return air tem-

perature falls one

degree below this

setpoint.

Wet Bulb

Setpoint

WtblSt

Analog

Input

The economizer is

enabled if the

outdoor tempera-

ture or wetbulb
falls below this

setpoint.

0

80

Coil

Temperature

Setpoint

CoilTpSt

Analog

Input

This is the coil

suction tempera-

ture target during

dehumidifi cation

mode. Produces

dewpoint in the

supply air

approximately

10°F above this

setpoint.

35

70

Relief

Pressure
Setpoint

RfPrSt

Analog

Input

This is the target

building pressure

to be maintained

by the VFD Relief

signal.

-0.2

0.2

Indoor

Humidity

Setpoint

InRhSt

Analog

Input

If the indoor

humidity rises

above this set-

point, the unit will

activate the

Dehumidifi cation

Demand.

0

100

Unoccupied

Cooling

Offset

UnClOst

Analog

Input

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied

Cooling Setpoint

out by a user

adjustable amount.

If you do not want
Cooling to operate

during the

Unoccupied

Mode, use the
default setting

of 30°F for these

setpoints.

0

30

SNVTs for the VCM-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Unoccupied

Heating

Offset

UnHtOst

Analog

Input

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied

Heating Setpoint

out by a user

adjustable amount.

If you do not want
Heating to operate

during the Unoc-

cupied Mode, use

the default setting

of 30°F for these

setpoints.

0

30

CO

2

Setpoint

CO2St

Analog

Input

When the CO

2

level rises above

the CO

2

Protection

Limit Max Level,

the Economizer’s

Minimum Position

will begin to reset

open proportion-

ally between the

CO

2

Protection

Limit Max Level

Setpoint and the

Reset Range

Setpoint.

0

3000

Minimum

Outside Air

Setpoint

MinEcoSt

Analog

Input

This is the

minimum position

of the economizer

in the occupied

modes.

1

100

Static

Pressure
Setpoint

DuctPrSt

Analog

Input

This is the target

duct pressure to

be maintained by

the VFD blower

signal.

0.01

3

Preheater

Setpoint

PreHtSp

Analog

Input

Low Outside Air

Ambient

Protection Set-

point

0

100

Outdoor

Air CFM

Setpoint

OACfmSt

Analog

Input

Minimum desired

Outdoor Air CFM.

0.10 K

200 K

Outdoor Air

CFM Reset

Limit

OACfmRs

Analog

Input

Maximum desired

Outdoor Air CFM
when CO

2

reaches

its reset limit.

0.10 K

200 K

Advertising