Appendix e - sa controller lon parameters, Pt-link interface, Pt-link-lon – Orion System PT-Link-LON User Manual

Page 27: Technical guide 27

Advertising
background image

PT-Link Interface

PT-Link-LON

®

Technical Guide

27

Appendix E - SA Controller LON Parameters

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Control Status

CtrlSts

Analog

Output

Current operational status.

Occupied/

Mode

Enable

Cooling

Setpoint

Mirror

ClSt

Analog

Output

Occupied/ Mode Enable Cooling

Setpoint Mirror.

Control

Temperature

CtrlTp

Analog

Output

Current value of the control

temperature sensor.

Duct Static

Pressure

DuctPr

Analog

Output

Current value of the duct static

pressure sensor.

Economizer

Position

EcoPos

Analog

Output

Current position of the

economizer damper.

Occupied/

Mode

Enable

Heating

Setpoint

Mirror

HtSt

Analog

Output

Occupied/ Mode

Enable Heating Setpoint Mirror.

Modulating

Gas Valve

Position

MdHt-

2Pos

Analog

Output

Current position of MODGAS II

modulating gas valve control.

Reheat Value

Position

Rt2Pos

Analog

Output

Current position of MHGRV

modulating hot gas reheat

valve control.

Indoor

Humidity

InRh

Analog

Output

Current value of the indoor

humidity sensor.

Space

Temperature

SpcTp

Analog

Output

Current value of the space

temperature sensor.

Current

Supply Air

Setpoint

SaTpStM

Analog

Output

Current SAT Cooling or Heating

setpoint if there is no reset source;

Current calculated SAT setpoint

with Reset Source.

Supply Air

Temperature

SaTp

Analog

Output

Current value of the supply air

temperature sensor.

Temperature

Demand

TpDmnd

Analog

Output

Based on the comparison between

the current Control Temperature

and the Heating or Cooling Set-

point Temperatures. Does not work

for supply air control.

VFD Blower

Fan

VfdBw-

Pos

Analog

Output

Current position of the VFD

blower fan signal.

Application

Software

Version

AppVer

Analog

Output

Current version of the software in

the unit.

Coil

Temperature

Setpoint

CoilTpSt

Analog

Output

Current Coil Temperature Setpoint.

Dewpoint

Setpoint

Mirror

DptStM

Analog

Output

Mirror of the DPtSt “read only.”

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Indoor RH

Setpoint

Mirror

InRhStM

Analog

Output

Mirror of the InRhSt “read only.”

Modulating

Cool

Position

MdClPos

Analog

Output

Current position of the modulating

cooling signal (Chilled water or

digital compressor).

Modulating

Heat

Position

MdHtPos

Analog

Output

Current position of the modulating

heating signal (hot water or SCR

heat).

Unit Mode

UnitMode

Analog

Output

Needed only in legacy application.

Coil

Temperature

CoilTp

Analog

Output

Current coil temperature reading

added on version 1.09.

Modulating

Compressor 2

Position

MdCmp2

Analog

Output

Current position of the 2nd Stage

of Compressor Modulation.

Head

Pressure 1

HdPr1

Analog

Output

Head Pressure for 1st unit.

Head

Pressure 2

HdPr2

Analog

Output

Head Pressure for 2nd unit.

Entering Air

Temperature

EaTp

Analog

Output

Temperature of the air that is

entering the unit.

Entering

Water

Temperature

EwTp

Analog

Output

Temperature of the water that is

entering the unit.

Entering Air

Humidity

EaRh

Analog

Output

Relative Humidity

of the Entering Air.

Coil

Temperature 2

CoilTp2

Analog

Output

Current Coil

Temperature for 2nd unit.

Entering Air

Dewpoint

EaDpt

Analog

Output

Current Entering Air Dewpoint

Water Side

Economizer

Bypass

WSEByp

Analog

Output

Current Water Side Economizer

Bypass Position for 1st unit.

Water Side

Economizer

Bypass 2

WSEByp2

Analog

Output

Current Water Side Economizer

Bypass Position for 2nd unit.

Condenser

Position 1

CdPos1

Analog

Output

Current Condenser Position

for 1st unit.

Condenser

Position 2

CdPos2

Analog

Output

Current Condenser Position

for 2nd unit.