Appendix f - vcm lon parameters, Pt-link-lon, Technical guide – Orion System PT-Link-LON User Manual

Page 34: Pt-link interface 34, Snvts for the vcm controller

Advertising
background image

PT-Link-LON

®

Technical Guide

PT-Link Interface

34

Appendix F - VCM LON Parameters

SNVTs for the VCM Controller

Binary Output SNVTs are SNVT_lev_disc

All other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Coil

Temperature

Setpoint

CoilTpSt

Analog

Input

This is the coil

suction temperature

during

dehumidifi cation

mode. Produces

dewpoint in the

supply air

approximately

10°F above this

setpoint.

35

70

Heating

Enabled

HtEnbl

Binary
Output

Status that

indicates that

mechanical heating

is enabled.

High

Supply Air

Temperature

Alarm

HiSaAlm

Binary
Output

The Supply Air
has risen above

the Hi SAT Cutoff

Setpoint. Heating

stages begin to de-

activate and the fan

continues to run.

Low

Supply Air

Temperature

Alarm

LoSaAlm

Binary
Output

The Supply Air has

fallen below the Hi

SAT Cutoff Setpoint

and cooling stages

will begin to deacti-
vate. If the unit is in

Economizer, Vent,

or Heating Mode

the Supply Fan will

shut off.

MODGAS

II

Connected

MdHt2Ins

Binary
Output

Status that indicates

the MODGAS II

controller is

connected.

Proof of

Flow

Confi gured

PofCfg

Binary
Output

Status that indicates

the proof of fl ow

function has been

confi gured.

REHEAT II

Connected

Rt2Ins

Binary
Output

Status that indicates

the MHGRV

controllers is

connected to the

system.

Warm Up

Mode

Active

WmupDmnd

Binary

Output

Status that indicates

the control is in the

Warm-up mode.

Mechanical

Cooling

Alarm

MchClAlm

Binary
Output

Compressor Relays

are enabled but

the Supply Air

Temperature has

not fallen 5°F w/in

a user-adjustable

time period. This

does not indicate

compressors are

active and will not

shut the unit down.

SNVTs for the VCM Controller

Binary Output SNVTs are SNVT_lev_disc

All other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Mechanical

Heating

Alarm

MchHtAlm

Binary
Output

Heating Mode has

been initiated but the
Supply Air Tempera-

ture has not risen 5°F

w/in a user-adjustable

time period. This

does not indicate heat

stages are active and
will not shut the unit

down.

Dirty Filter

Detected

DrtFlAlm

Binary
Output

Alarm that indicates

the fi lters are dirty.

Control

Temperature
Cool Failure

CtrlTpCF

Binary
Output

This alarm is

activated if the con-

trol temperature does

not get within 5°F to
the occupied cooling

setpoint in an hour

in the cooling mode.

This alarm is not

used in 100% outside
air units or supply air

control.

Control

Temperature
Heat Failure

CtrlTpHF

Binary
Output

This alarm is

activated if the con-

trol temperature does

not get within 5°F to
the occupied heating

setpoint in an hour

in the heating mode.

This alarm is not

used in 100% outside
air units or supply air

control.

Dehu-

midifi cation

Demand

DehmDmnd

Binary
Output

Status that indicates

a demand for

dehumidifi cation.

Outdoor Air

Temperature

Lost

OaTpAlm

Binary
Output

Alarm that indicates a

failure in the outdoor

air temperature.

Smoke

Detected

Alarm

SmokeAlm

Binary
Output

Alarm that indicates

the Smoke sensor has

been activated.

Space

Temperature

Sensor Lost

SpcTpAlm

Binary
Output

Alarm that indicates

a failure in the space

temperature sensor.

On Board

Relay 1

OnRly1

Binary
Output

Current status of

relay 1.

On Board

Relay 2

OnRly2

Binary
Output

Current status of

relay 2.

On Board

Relay 3

OnRly3

Binary
Output

Current status of

relay 3.

On Board

Relay 4

OnRly4

Binary
Output

Current status of

relay 4.

On Board

Relay 5

OnRly5

Binary
Output

Current status of

relay 5.

Advertising