Appendix C - VCM-X Modular and WSHP LON Parameters

SNVTs for the VCM-X WSHP (Coil)

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Modulating

Compressor 2

MdCmp2

Analog

Output

Current position of the

2nd Stage of Compressor

Modulation.

Head Pressure 1

HdPr1

Analog

Output

Head Pressure for

1st Compressor

Head Pressure 2

HdPr2

Analog

Output

Head Pressure for

2nd Compressor

Condenser

Fan 1

CdFan1

Analog

Output

Condenser Fan 1

Signal Status

Condenser

Fan 2

CdFan2

Analog

Output

Condenser Fan 2

Signal Status

Water Temp. A

WaterTpA

Analog

Output

Current water

temperature.

Compressor A

Low Suction

Pressure Alarm

A1LSPAlm

Binary
Output

Alarm that indicates

Suction Pressure for Circuit A

is below the Low

Suction Pressure Cooling

(Heating) Setpoint.

Compressor A

Lockout Alarm

A1LktAlm

Binary
Output

Alarm that indicates Circuit A

Compressors are locked out.

Compressor B

Low Suction

Pressure Alarm

B1LSPAlm

Binary
Output

Alarm that indicates

Suction Pressure for Circuit B

is below the Low

Suction Pressure Cooling

(Heating) Setpoint.

Compressor B

Lockout Alarm

B1LktAlm

Binary
Output

Alarm that indicates Circuit B

Compressors are locked out.

Low Water

Temperature

Alarm

LWT1Alm

Binary
Output

Alarm that indicates water tem-

perature is below the Leaving

Water Safety

Setpoint (Heating only).

Proof of Water

Flow Alarm

POWF1Alm

Binary
Output

Alarm that indicates no

Proof of Water Flow.

Module

Communica-

tions

Alarm

ComMAlm

Binary
Output

Alarm that indicates that one

or more Modules are not com-

municating with the VCM-X

WSHP Controller.