INSTALLATION INSTRUCTIONS

CAUTION:

This water heater

MUST ONLY be used with the following water

supply conditions to prevent product damage and

operation failure.
Clean, potable water free of corrosive chemicals,

sand, dirt, or other contaminates.

Inlet water temperatures above 32°F (0°C), but

not exceeding 120°F (49°C).

DO NOT reverse the HOT and COLD water

connections.

DO NOT connect this water heater to water lines

previously used for space heating. All water

piping and components shall be suitable for

potable water.

With recommended water quality (see chart).

Thermal Expansion

A thermal expansion tank will be required if the

water heater is installed in a recirculation system.

This prevents damage to the heater, related piping,

and the relief valve.

NOTICE:

Replacing the relief valve will

not correct the problem!

The expansion tank is designed with a built-in air

cushion that compresses as the system pressure

increases. This relieves the over-pressure condition

and eliminates the repeat operation of the relief

valve.
For other approved methods of thermal expansion,

contact an installing contractor, water supplier, or

plumbing inspector.

Water Supply Connections

CAUTION:

IMPORTANT—Do

not apply heat to the HOT or COLD water

connections. If sweat connections are used, sweat

tubing to the adapter before fitting the adapter

to the water connections on the water heater.

Any heat applied to the water supply fittings will

permanently damage the internal components of

the water heater.

NOTICE:

In cold environments, ice can

accumulate in the water heater’s connectors. Plug

in the water heater power cord for approximately

10 minutes before making these connections. This

will melt any ice buildup.

Plumbing should be carried out by a qualified

plumbing contractor in accordance with local

codes.
Only use approved plumbing materials.
The minimum diameter of all water pipes should

be 3/4 in. (1.9 cm).
To conserve energy and to prevent freezing,

insulate both COLD and HOT water supply lines.

Do not insulate the drain line or pressure-relief

valve.

Chart for Recommended Water Quality Levels

pH

TDS (Total

Dissolved Solids)

Free Carbon

Dioxide (CO

2

)

Total

Hardness

Aluminum

Chlorides

Copper

Iron

Manganese

Zinc

6.5–8.5

Up to 500 mg/L

Up to 15 mg/L

Up to

200 mg/L

Up to

0.2 mg/L

Up to

200 mg/L

Up to

1.0 mg/L

Up to

0.3 mg/L

Up to

0.05 mg/L

Up to

1.0 mg/L

Water Supply

Plumbing

Advertising