Gas Supply

Gas Supply Installation

Install the manual gas appliance shut-off valve

to the gas connection at the water heater. The

shut-off is supplied with the water heater.

Install a ground joint union or ANSI design-

certified semi-rigid or flexible gas appliance

connector to the open end of the manual gas

appliance shut-off valve. The (NFGC) ANSI

Z223.1 and CSA B149.1 codes mandate the

use of manual gas shut-off valves.

Install a manual gas supply line shut-off valve

to the end of the gas supply line.

NOTICE:

Lever-type gas shut-offs

should all be T-handle type.

Using the proper-size piping, fittings, and

components, build the gas supply line to the

water heater.

NOTICE:

The gas supply line should

be a minimum of 3/4-in. (1.9-cm) black steel

pipe or other approved gas piping material.

Install a sediment trap at the lowest portion of

the gas line.

The inlet gas pressure to the water heater must

NOT exceed 10.5 in. w.c. (2.6 kPa) for natural

gas and 14 in. w.c. (3.5 kPa) for LP gas. For

purposes of input adjustment, the minimum inlet

gas pressure (with main burner on) is shown on

the water heater rating plate. If high or low gas

pressures are present, contact your gas supplier

for correction.