Installation instructions, Venting for direct-vent water heater (cont.), Venting – Paloma PHH-32 part 2 User Manual

Page 8: Vertical vent terminal location

Advertising
background image

44

Vertical Vent Terminal Location

A, B, C, D

12" Min.

(300 mm)

Vent Pipe

Through Roof

Optional

The following chart with diagrams details the minimum dimensional information needed to determine the

proper location of the vertical vent terminal for direct-vent indoor tankless water heaters:

Location

U.S. Installation
Requirements

1

Canadian Installation
Requirements

2

A = Minimum clearance above the roof level.

12 in. (30.5 cm) above roof level.

18 in. (45.7 cm) above roof level.

B = Minimum clearance above anticipated snow

level.

12 in. (30.5 cm) above anticipated
snow level.

12 in. (30.5 cm) above anticipated
snow level.

C = Maximum clearance above roof level (without

additional support for vent pipe).

24 in. (61 cm) above roof level.

24 in. (61 cm) above roof level.

D = Maximum clearance above anticipated snow

level (requires additional vent support).

24 in. (61 cm) above anticipated snow
level.

24 in. (61 cm) above anticipated
snow level.

E = Required vent clearance from any gable,

dormer, or other roof structure with building
interior access (i.e., vent, window).

4 ft. (1.2 m)

4 ft. (1.2 m)

F = Required vent clearance from any forced air

inlet, including dryer and furnace air inlets.

10 ft. (3 m)

6 ft. (1.8 m)

G = Minimum/maximum horizontal distance

between vent terminals

5.5 in. (14 cm)/24 in. (61 cm)

5.5 in. (14 cm)/24 in. (61 cm)

1 In accordance with current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
2 In accordance with current CSA B149.1 Installation Codes.

The vertical intake air termination requires a

return bend or two short or long sweep radius 90°

elbows to keep the inlet downward and prevent

entry of rain. Refer to figure above for the proper

location of the air intake with respect to the

exhaust outlet termination. The vertical exhaust

outlet termination is a 2-inch or 3-inch pipe which

terminates at least 12 inches above the air intake

termination. The air intake and exhaust outlet

terminations must be at least 12 inches above the

roof line or anticipated snow levels.

Venting

INSTALLATION INSTRUCTIONS

Venting for Direct-Vent Water Heater (cont.)