INSTALLATION INSTRUCTIONS

Gas Supply

Gas Piping

Pipe-Sizing Procedure – Example

The gas supply must be capable of handling the

entire gas load at the location. Gas line sizing

is based on gas type, the pressure drop in the

system, the gas pressure supplied, and gas line

type. For gas pipe sizing in the United States,

refer to the National Fuel Gas Code, NFPA 54. For

Canadian gas pipe sizing, refer to the Natural Gas

and Propane Installation Code CAN/CSA B149.1.

The information below is provided as an example.

The appropriate table from the applicable code

must be used.
1. Determine the cubic feet per hour of gas

required by dividing the gas input (on the rating

plate) by the heating value of the gas (available

from the local gas company). The gas input

needs to include all gas products at the location

and the maximum BTU usage at full load when

all gas products are in use.

2. Use the table for your gas type to find the pipe

size required for your cubic feet per hour of gas

and your pipe length.
Example: The heating value of propane gas for

your location is 2500 BTU/FT

3

. The gas input

of the tankless water heater is 199,900 BTU/

HR. Additional appliances at the location require

75,000 BTU/HR. Therefore, the cubic feet per

hour = (199,900 + 75,000)/2500 = 109 FT

3

/HR.

If the pipe length is 100 ft., then the 3/4-inch

pipe size capable of supplying 197 FT

3

/HR of

propane gas will be adequate.

Gas Input of

Cubic Feet Water Heater (BTU/HR)

Per Hour (CFH) = Heating Value of Gas (BTU/FT

3

)

Pipe-Sizing Table – Natural Gas

Schedule 40 Metallic Pipe

Inlet Pressure: Less than 2 psi (55 inches W.C.)

Pressure Drop: 0.3 inches W.C.

Specific Gravity: 0.60

(Capacity in cubic feet per hour)

Length

Pipe Size (inches)

3/4

1

1 1/4

1 1/2

10

273

514

1060

1580

20

188

353

726

1090

30

151

284

583

873

40

129

243

499

747

50

114

215

442

662

60

104

195

400

600

70

95

179

368

552

80

89

167

343

514

90

83

157

322

482

100

79

148

304

455

125

70

131

269

403

150

63

119

244

366

175

58

109

224

336

200

54

102

209

313

Pipe-Sizing Table – Propane Gas

Schedule 40 Metallic Pipe

Inlet Pressure: 11.0 inches W.C.

Pressure Drop: 0.5 inches W.C.

Specific Gravity: 1.50

(Capacity in cubic feet per hour)

Length

Pipe Size (inches)

1/2

3/4

1

1 1/4

10

291

608

1150

2350

20

200

418

787

1620

30

160

336

632

1300

40

137

287

541

1110

50

122

255

480

985

60

110

231

434

892

80

101

212

400

821

100

94

197

372

763

125

89

185

349

716

150

84

175

330

677

175

74

155

292

600

200

67

140

265

543

Refer to current National Fuel Gas Code, NFPA 54.