Installation instructions, Water supply (cont.), Notices – Paloma PHH-32 part 2 User Manual

Page 14: Plumbing, Relief valve

Advertising
background image

50

INSTALLATION INSTRUCTIONS

Plumbing

Water Supply (cont.)

Relief Valve

A new pressure-relief valve, complying with the

Standard for Relief Valves and Automatic Gas

Shut-Off Devices for Hot Water Supply Systems,

ANSI Z21.22/CSA 4.4, must be installed at the

HOT water outlet connection of the water heater

during installation. Local codes shall govern the

installation of any relief valves or place of purchase

for availability and installation information.

NOTICES:

The following drawing illustrates a pressure-only

relief valve. If local codes require a combination

temperature and pressure-relief valve, you may

need to install an extension piece to ensure that

the valve probe is not directly in the flow path of

the water.

If local codes require that a temperature and

pressure-relief valve be installed, the manufacturer

recommends a type 40XL Watts temperature and

pressure-relief valve or equivalent model be used.

Manual operation of relief valves should be

performed at least once a year.

If the relief valve on the system discharges

periodically, a problem exists. Turn off the water

heater, unplug the unit, and call for service.

One end of the relief valve discharge line connects

to the HOT water outlet pipe as shown above.

The other end of the pipe should be routed to a

suitable drain to eliminate potential water damage.

For safe operation of the water heater, be sure

that:
The pressure rating of the relief valve must not

exceed 150 psi (1,034 kPa) or the maximum

working pressure of the water heater. (See the

rating plate on the water heater.)

The BTUH rating of the relief valve must equal or

exceed the BTUH input of the water heater. (See

the rating plate on the water heater.)

No valve of any type should be installed between

the relief valve and the water heater.

Discharge from the relief valve should be piped

to a suitable drain. Piping used should be of a

type approved for the distribution of hot water.

HOT and COLD water lines should be insulated

up to the water heater. See page 51.

The discharge line must be NO SMALLER than

the outlet of the relief valve. The drain line must

pitch downward to allow for complete drainage

of the line and the valve.

The end of the discharge line should not be

threaded or concealed and should be protected

from freezing. No valve of any type, restriction,

or reducer coupling should be installed in the

discharge line.

Relief

Valve

Union

Union

Cold Water Supply

Shut-Off Valve

Cold Water

Supply Inlet

Hot Water

Supply Outlet

Relief Valve

Discharge Line

Advertising
This manual is related to the following products: