Installation instructions, Warning, Venting – Paloma PHH-32 part 2 User Manual

Page 3: Horizontal vent considerations, Indoor tankless water heaters, Outdoor tankless water heaters

Advertising
background image

39

INSTALLATION INSTRUCTIONS

Venting

Horizontal Vent Considerations

WARNING:

Moisture in the flue gas

will condense as it leaves the vent terminal. In cold

weather this condensate can freeze on the exterior

wall, under the eaves, and on surrounding objects.

Some discoloration to the exterior of the building

is to be expected. However, improper location

or installation can result in severe damage to the

structure or exterior finish of the building.

Do not install vent terminals under any patio or

deck.

Do not locate vent terminal on the side of a

building with prevailing winter winds. This will

help prevent water lines from freezing and

moisture from freezing on walls and under

eaves.

Do not locate vent terminal too close to

shrubbery, since flue gases may damage them.

All painted surfaces should be primed to

lessen the chance of physical damage. Painted

surfaces will require maintenance.

Guard against accidental contact with people

and pets.

INDOOR TANkLESS WATER

HEATERS

WARNING:

For multiple-unit

installation, a minimum distance between vent

terminations must be maintained to prevent

recirculation of vent gases. Maintain a center-

to-center distance between each pair of vent

terminations of 24 in. (61 cm) for a two-unit

installation; 24 in. (61 cm) and 36 in. (91.4 cm) for

an installation of three units; and 24 in. (61 cm),

36 in. (91.4 cm), and 24 in. (61 cm) for an

installation of four units.

Do not terminate vent directly on brick or

masonry surfaces. Use rust-resistant, sheet-

metal backing plate of 1 sq. ft. (30 sq. cm)

behind the vent.

Caulk all cracks, seams, and joints within

6 ft. (1.8 m) of the vent terminal.

Caulk around wall faceplate for weather-tight

seal.

Do not extend exposed vent pipe of indoor

water heaters outside of the building.

This water heater requires its own separate

venting system.

Do not connect the exhaust

vent to an existing vent pipe or chimney.

OUTDOOR TANkLESS WATER

HEATERS

Install outdoor water heater such that air inlet

and flue outlet are above anticipated snow level.

Rising moisture will collect under eaves.

Inside

Corner

Caulk

Caulk

Caulk

Caulk

If soffit vent is too close,

block off and install new

vent at another location.

6' (1.8 m) Caulk zone or

to edge of window etc.,

starting within 6' (1.8 m)

4'

(1.2 m)

Rising moisture will collect under eaves.

Inside

Corner

Caulk

Caulk

Caulk

If soffit vent is too close,

block off and install new

vent at another location.

6' (1.8 m) Caulk zone

or to edge of window

etc., starting within

6' (1.8 m)

4'

(1.2 m)

12"

(300 mm)