Venting installation instructions – Desa CD36TN-M User Manual

Page 13

Advertising
background image

www.desatech.com

118531-01A

13

H

V

GROUND FLOOR INSTALLATION

Recommended CHVK-58 Corner Horizontal

Vent Kit:

• Installation using cabinet surrounds

• Through the wall using square termination

(up to 24" horizontal pipe)

• Corner installation (Using one 6" vertical sec-

tion, one 90° elbow and a maximum of 24" of

horizontal pipe)

VENTING INSTALLATION

INSTRUCTIONS

Continued

Figure 14 - Horizontal Termination

Configuration For Corner Installation

Using One 90° Elbow

Figure 15 - Horizontal Termination

Configuration with Vertical Rise and One

90° Elbow

Required

Vertical (V)

Vertical (V)

Vertical Pipe

Allowable

Horizontal (H)

51"

"

" Max.

5

1

/

4

" Min.

1'

30" Max.

9

1

/

4

" Min.

'

4" Max.

81

1

/



" Min.

3'

98" Max.

94" Min.

4'

1" Max.

10" Min.

5'

14" Max.

159" Min.

9'

0' Max.

TO

H

Wall
Firestop

Straight/
Adjustable
Pipe 4" Max.

Horizontal
Square
Termination

90°
Elbow

Corner Installation

Vertical (V)

Horizontal (H)

51" Min.

3

1

/



" Max

90° Elbow

Wall
Firestop

Square
Termination

Not to Exceed
(H) Limits

As
Required
for (V),
See Chart
for Pipe
Section
Required

Horizontal Termination Configurations

Figures 14 through 18 show different configura-

tions and alternatives for venting with horizontal

termination. Each figure includes a chart with

critical minimum and maximum dimensions which

MUST be met. IMPORTANT: Remember that a

horizontal run of venting must have a 1/4" rise for

every 12" of run toward the termination.