Venting installation instructions – Desa CD36TN-M User Manual

Page 15

Advertising
background image

www.desatech.com

118531-01A

15

VENTING INSTALLATION INSTRUCTIONS

Continued

INSTALLATION FOR vERTICAL
TERMINATION

Note:

Vertical restrictor must be installed in all

vertical installations.

1. Determine the route your vertical venting

will take. If ceiling joists, roof rafters or other

framing will obstruct the venting system,

consider an offset (see Figure 19) to avoid cut-

ting load bearing members. Note: Pay special

attention to these installation instructions for

required clearances (air space) to combustibles

when passing through ceilings, walls, roofs,

enclosures, attic rafters, etc. Do not pack air

spaces with insulation. Also note maximum

vertical rise of the venting system and any

maximum horizontal offset limitations.

2. Set the fireplace in desired location. Drop a

plumb line down from the ceiling to the posi-

tion of the fireplace exit flue. Mark the center

point where the vent will penetrate the ceiling.

Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof

to the locating hole in the ceiling. Mark the

center point where the vent will penetrate the

roof. Drill a small locating hole at this point.

Figure 19 - 45° and 30° Offset with Wall

Strap

Roof
Flashing

Wall
Strap

45°

Elbows

WS-58
Wall Strap

 -  x 4
Vertical
Header

OSR58-30
30° Offset
Return

Horizontal
Frame Member

Flat Ceiling Installation

1. Cut a 10

3

/

4

" square hole in the ceiling using

the locating hole as a center point. The open-

ing should be framed to 10

3

/

4

" x 10

3

/

4

" inside

dimensions, as shown in Figure 11 on page

11 using framing lumber the same size as the

ceiling joists. If the area above the ceiling is

an insulated ceiling, you must use the firestop

thimble and special firestop included with the

kit to prevent insulation from contacting the

vent pipe (see Thimble Installation, page 16).

Otherwise, install firestop below the framed

hole. The firestop should be installed with no

less than three nails per side (see Figure 20).

2. Assemble the desired lengths of pipe and

elbows necessary to reach from the fireplace

flue up through the firestop. Be sure all pipe

and elbow connections are fully twist-locked

(see Figure 10, page 11).

3. Cut a hole in the roof using the locating hole

as a center point. (Cover any exposed open

vent pipes before cutting hole in roof.) The

10

3

/

4

" x 10

3

/

4

" hole must be measured on

the horizontal; actual length may be larger

depending on the pitch of the roof. There

must be a 1" clearance from the vent pipe to

combustible materials. Frame the opening as

shown in Figure 11, page 11.

4. Connect a section of pipe and extend up

through the hole.

Note: If an offset is needed to avoid obstruc-

tions, you must support the vent pipe every 3

feet. Use wall straps for this purpose (see Fig-

ure 19). Whenever possible, use 45° elbows

instead of 90° elbows. The 45° elbow offers

less restriction to the flow of the flue gases

and intake air.

Figure 20 - Installing Firestop

If area above is a room, install firestop
above framed hole.

If area above is an insulated area, install
firestop below framed hole.

Advertising