Venting installation instructions – Desa CD36TN-M User Manual

Page 16

Advertising
background image

www.desatech.com

118531-01A

1

5. Place the flashing over the pipe section(s)

extending through the roof. Secure the base of

the flashing to the roof and framing with roof-

ing nails. Be sure roofing material overlaps the

top edge of the flashing as shown in Figure 19,

page 15. There must be a 1" clearance from

the vent pipe to combustible materials.

6. Continue to add pipe sections until the height of

the vent cap meets the minimum building code

requirements described in Figure 9 on page 9.

Note:

You must increase vent height for steep roof

pitches. Nearby trees, adjoining rooflines, steep

pitched roofs and other similar factors may cause

poor draft or down-drafting in high winds. Increas-

ing the vent height may solve this problem.

7. Twist-lock the vent cap onto the last section

of vent pipe.

Note:

If the vent pipe passes through any occupied

areas above the first floor, including storage spaces

and closets, you must enclose pipe. You may frame

and sheetrock the enclosure with standard construc-

tion material. Make sure and meet the minimum

allowable clearances to combustibles. Do not fill

any of the required air spaces with insulation.
Thimble Installation

1. Plumb and locate knockout area for vent pipe.

2. Cut and frame ceiling joist to dimensions

shown in Figure 11, page 11.

3. Determine where firestop plate should be at-

tached to thimble by test-fitting thimble into

framing. Thimble should be at or above the

height of the insulation.

4. Attach thimble into firestop plate using 4 hex

screws provided (see Figure 21).

VENTING INSTALLATION

INSTRUCTIONS

Continued

Figure 22 - Vertical Venting

Configuration using Three 90° Elbows

(Vertical Round High Wind Termination)

Venting with Three 90° Elbows

Vertical (V)

Horizontal (H

1

) +

Horizontal (H

2

)

8' Min.

5' Max

10' Min.

8' Max

1' Min.

11' Max

14' Min.

14' Max

1' Min.

1' Max

18' Min.

0' Max

40' Min.

0' Max

90° Elbow

Note: Install a
VR-58 vertical
restrictor ring
into inner pipe
section prior to
attaching vent
termination
cap.

Framing

Top of
Thimble
Should
Measure
to Top of
Insullation

Hex Screw
to Attach
Firestop to
Thimble

Phillips Screws
to Attach
Firestop to
Framed Hole

Firestop

Figure 21 - Installing Thimble with

Firestop

5. Refit assembly into opening and attach to

framing with 8 phillips screws provided (see

Figure 20, page 15).

6. Thimble installation is ready to receive vent

pipe. Follow venting installation instructions.

Vertical Termination Configurations for
Top Vent

Figures 22 through 25 show four different con-

figurations for vertical termination.
VERTICAL VENT INSTALLATIONS USING
MULTIPLE 90° ELBOWS