6 MECHATROLINK Option Unit Parameters

YASKAWA ELECTRIC

TOBP C730600 50C YASKAWA 1000-Series Option SI-T3 Installation Manual

25

F6-23

<5> <8>

{

MECHATROLINK

Monitor Selection (E)

Sets the MECHATROLINK-II monitor (E).

Default: 0H

Min.: 0H

Max.: FFFFH

F6-24

<5> <9>

{

MECHATROLINK

Monitor Selection (F)

Sets the MECHATROLINK-II monitor (F).

Default: 0H

Min.: 0H

Max.: FFFFH

F6-25

{

Operation Selection at

Watchdog Error (E5)

Determines unit response when an E5 error is

detected during communications with the

MECHATROLINK-II Option

0: Ramp to stop. Decelerate to stop using the

deceleration time in C1-02.

1: Coast to stop.

2: Fast Stop. Decelerate to stop using the

deceleration time in C1-09.

3: Alarm only.

Default: 1

Range: 0 to 3

F6-26

{

{

MECHATROLINK

bUS Errors Detected

Sets the number of option communication errors

(bUS).

Default: 2

Min.: 2

Max.: 10

<1> To start and stop the drive with the MECHATROLINK master device using serial communications, set b1-02 to 3.

To control the frequency reference of the drive via the master device, set b1-01 to 3.

<2> To start and stop D1000 with the MECHATROLINK master device using the voltage reference of the D1000, set

b1-18 to 3.

<3> This parameter is available in the D1000.

<4> If set to 3, then the unit will continue to operate when a fault is detected. Take proper measures such as installing

an emergency stop switch.

<5> Power must be cycled in order for any setting changes to take affect.

<6> All station addresses must be unique. If set to 20 or 3F, a Station Address Error (AEr) will occur and the ERR light

will turn on.

<7> All station addresses must be unique. If set to 60 or 7F, a Station Address Error (AEr) will occur and the ERR light

will turn on.

<8> Setting byte 10 of INV_CTL to 0EH enables the register set by F6-23. Byte 11 and 12 of the response data enable

the register content set by F6-23.

Refer to the SI-T3 Technical Manual for detail.

<9> Setting byte 10 of INV_CTL to 0FH enables the register set by F6-24. Byte 11 and 12 of the response data enable

the register content set by F6-24.

Refer to the SI-T3 Technical Manual for detail.

INV: Drive Parameter, CNV: Energy-Saving Unit Parameter

No.

INV CNV

Name

Description

Values