7 Troubleshooting

YASKAWA ELECTRIC

TOBP C730600 50C YASKAWA 1000-Series Option SI-T3 Installation Manual

29

Minor Faults and Alarms

Operator Display

Minor Fault Name

AEr

Station Address Error
MECHATROLINK-II Option is set to an address outside the allowable setting range.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Address outside the

specified address range

Set F6-20 to an address within the specified range.

YES

Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Communication wiring is

faulty, there is a short

circuit, or something is not

connected properly.

Check for wiring errors.

Correct the wiring.

Remove and ground shorts and reconnect loose wires.

YES

Programming error on the

master side

Check communications at start-up and correct programming

errors.

Communication circuitry is

damaged.

Perform a self-diagnostics check.

Replace the unit if the fault continues to occur.