5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 51F 1000-Series Option PG-F3 Installation Manual

19

5.

Wire the motor PG encoder to the terminal block on the option.

Wiring EnDat 2.1/01 or EnDat 2.2/01 Encoders

Wire the motor PG encoder to the terminal block on the option using a HEIDENHAIN 17-

conductor cable. Refer to

Figure 6

and

Figure 7

for wiring instructions. Refer to

Figure 8

for the connection diagram.

The signal “Sensor Up”must be connected to terminal IP on the PG-F3 option for cables

longer than 10 m. Additionally, the “Sensor 0 V”must be connected to terminal IG. Refer

to

Table 8

and

Table 9

for a detailed description of the option terminal functions.

Connection Diagram

Figure 8 PG-F3 Option and PG Encoder Connection Diagram (EnDat 2.1/01, EnDat 2.2/01)

<1> Properly connect the cable shield to terminal IG on the option Terminal Block TB2 or remove the ground

connection on both ends.

<2> Ground the shield on the PG encoder side and the drive side. If noise problems arise in the PG encoder signal,

remove the shield ground from one end of the signal line or remove the shield ground connection on both ends.

0V

IP

IP

IG

IG

CN3

8V
5V

a–

M

CN5-C

YASKAWA

Drive

PG-F3
Option

U/T1

V/T2

W/T3

R/L1
S/L2
T/L3

FE

B+

B–

A–

A+

DT

DT

CK

CK

TB1,TB2

FE

a+

b+

b–

Cable

(by HEIDENHAIN)

EnDat 2.1/01,
EnDat 2.2/01
encoder

A pulse monitor signal

B pulse monitor signal

main circuit terminal control circuit terminal

<2>

Shielded cable

<1>

Ground wire