7 troubleshooting – Yaskawa Option PG-F3 Motor Encoder Feedback User Manual

Page 37

Advertising
background image

7 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 51F 1000-Series Option PG-F3 Installation Manual

37

Digital Operator Display

Fault Name

oFC01

Option Connection Error at drive port CN5-C

Cause

Possible Solution

Option at drive port CN5-C was
changed during run.

Switch the power off and reconnect the option.

Digital Operator Display

Fault Name

oFC50

PG Encoder Option A/D Conversion Error
Error with the A/D conversion level (VCC level), or A/D conversion timed out.

Cause

Possible Solution

The option is damaged.

Replace the option.

Digital Operator Display

Fault Name

oFC51

PG Encoder Option Analog Circuit Error
Incorrect signal level (+2.5 V signal)

Cause

Possible Solution

The option is damaged.

Replace the option.

Digital Operator Display

Fault Name

oFC52

PG Encoder Communication Timeout
Serial encoder timed out waiting to receive data

Cause

Possible Solution

PG encoder wiring is incorrect.

Correct the wiring.

PG encoder cable is
disconnected.

Reconnect the cable.

F1-50 (Encoder selection) is
incorrect.

Set F1-50 (Encoder selection) according to the encoder connected to the drive.

Digital Operator Display

Fault Name

oFC53

PG Encoder Communication Data Error
Serial encoder CRC checksum error

Cause

Possible Solution

PG encoder wiring is incorrect.

Correct the wiring.

PG encoder cable is
disconnected.

Reconnect the cable.

Digital Operator Display

Fault Name

oFC54

PG Encoder Error
Alarm reading EnDat absolute position data from the PG encoder
(OR flag from EnDat error for overvoltage, undervoltage, etc.)

Cause

Possible Solution

Power supply to PG encoder is
wired incorrectly.

Correct the wiring.