5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 51F 1000-Series Option PG-F3 Installation Manual

27

9.

Set drive parameters in

Table 10

for proper motor rotation.

Confirming Motor Rotation with EnDat 2.1/01, EnDat 2.2/01, or HIPERFACE

The leading pulse determines the motor rotation direction. A PG encoder signal with

leading A phase is considered to be rotating forward (counter-clockwise when viewing

rotation from motor load side).

Figure 10

Figure 13 Displacement of A and B Phases

After connecting the PG encoder outputs to the option, apply power to the drive and

manually rotate the motor and check the rotation direction by viewing monitor U1-05 on

the digital operator.

WARNING! Ensure the drive RUN circuit is locked out and a RUN command is not possible before

attempting to manually rotate the motor shaft with the drive powered on. Failure to comply may cause injury

to personnel due to inadvertant equipment movement.

Reverse motor rotation is indicated by a negative value for U1-05; forward motor rotation

is indicated by a positive value.

If monitor U1-05 indicates that the forward direction is opposite of what is intended, set

drive parameter F1-05 to 1 to switch the direction of how the option reads pulses from the

PG encoder output.

Note: If the drive is initialized using A1-03 =1110, 2220, or 3330, the value for F1-05 will reset to the

factory default and the parameter will need to be readjusted to switch the direction.

Confirming Motor Rotation with EnDat 2.2/22

EnDat 2.2/22 uses serial data transmission and lacks A and B phases, so it is necessary to

refer to monitor U1-05 to determine the direction of rotation.

After connecting the PG encoder outputs to the option, apply power to the drive and

manually rotate the motor and check the rotation direction by viewing monitor U1-05 on

the digital operator.

WARNING! Ensure the drive RUN circuit is locked out and a RUN command is not possible before

attempting to manually rotate the motor shaft with the drive powered on. Failure to comply may cause injury

to personnel due to inadvertant equipment movement.

Reverse motor rotation is indicated by a negative value for U1-05; forward motor

rotation is indicated by a positive value.
If the motor is rotating forward, but U1-05 reads that it is rotating in reverse,

switch the rotation direction for the PG1 encoder by setting parameter F1-05 to 1.

Note: If the drive is initialized using A1-03 = 1110, 2220, or 3330, the value for F1-05 will reset to the

factory default and the parameter will need to be readjusted to switch the direction.

A

B

The A phase leads, followed
by the B phase displaced at 90 degrees

Time

Phase

Phase