Power checks, Test procedure checklist – Yaskawa GPD 506/P5 Section Two User Manual
Page 3
Advertising
PP.P5G5.02Troubleshoot
Page 3
Rev. 06/11/2003
Power Checks
TEST PROCEDURE CHECKLIST
1. Remove the DC bus fuse and replace it with a 30W, 500 ohm resistor.
2. Apply power to terminals L1, L2, & L3.
3. Check the DC bus voltage.
4. Check the 15V power supply.
5. Check the (-15V) power supply. (GPD515/G5 only)
6. Check the isolated 24V power supply.
7. Check the output voltage waveform.
8. Check the gate firing pulses (if necessary).
9. Remove the 500 ohm resistor, re-install the DC bus fuse.
10. Run the motor.
11. Check the output current waveform.
12. Check the control board inputs and outputs.
13. Check the PG pulses. (GPD515/G5 only)
Check box when completed
Advertising