Practical examples of electrical tests, Low continuity measurement – Amprobe MEGATEST-1000 Megohmmeter User Manual

Page 26

Advertising
background image

6. PRACTICAL EXAMPLES OF ELECTRICAL TESTS

6.1 LOW

CONTINUITY MEASUREMENT


CONTINUITY MEASUREMENT ON PROTECTIVE CONDUCTORS

PURPOSE OF THE TEST

Check the continuity of:

protective conductors (PE), main equalising potential

conductors (EQP), secondary equalising potential
conductors (EQS) in TT and TN-S systems.

neutral conductors having functions of protective

conductors (PEN) in TN-C system.

NOTE: This test is to be preceded by a visual check verifying the existence of yellow-

green protective and equalising potential conductors as well as compliance of
the sections used with the standards’ requirements.

INSTALLATION PARTS TO BE CHECKED.

Equalising
potential node

Connect one of the
test leads to the
protective conductor
of the FM socket
and the other to the
equalising potential
node of the earth
installation.

Connect one of the
test lead to the
external mass (in
this case the water
pipe) and the other
to the earth
installation using for
example the
protective conductor
of the closest FM
socket.

Examples for continuity measurement on conductors

25

Advertising
This manual is related to the following products: