10. TECHNICAL SPECIFICATIONS

TECHNICAL FEATURES
Accuracy is indicated as [% of reading + number of digits]. It refers to the following
atmospheric conditions: a temperature of 23°C ± 5°C with a relative humidity < 75%.

Continuity

Test mode

Measuring range

(

)

Resolution

(

)

Accuracy

0.01 – 19.99

0.01

AUTO, R+, R-

20.0 – 99.9

0.1

±(2% Reading + 2 digit)

R+TIMER

R-TIMER

0.01 – 9.99

0.01

±(2% Reading + 2 digit)


Test current

>200mA DC up to 16

Ω (incluse the resistance of the calibration)

40mA DC from 16

Ω to 99.9Ω

Test current resolution

1mA

Open circuit Test Voltage

9V


Insulation resistance

Test voltage

(

)

Measuring range

(M

)

Resolution

(

)

Accuracy

0.01 – 19.99

0.01

20.0 – 49.9

0.1

±(2% Reading + 2 digit)

50

50.0 – 99.9

0.1

±(5% Reading + 2 digit)

0.01 – 19.99

0.01

20.0 – 99.9

0.1

±(2% Reading + 2 digit)

100

100.0 – 199.9

0.1

±(5% Reading + 2 digit)

0.01 – 19.99

0.01

20.0 – 199.9

0.1

200 - 249

1

±(2% Reading + 2 digit)

250

250 - 499

1

±(5% Reading + 2 digit)

0.01 – 19.99

0.01

20.0 – 199.9

0.1

200 - 499

1

±(2% Reading + 2 digit)

500

500 - 999

1

±(5% Reading + 2 digit)

0.01 – 19.99

0.01

20.0 – 199.9

0.1

200 - 999

1

±(2% Reading + 2 digit)

1000

1000 - 1999

1

±(5% Reading + 2 digit)


Automatic selection of the measuring range
Open circuit voltage

1,1 x Rated voltage test

Short circuit current

<3,0mA - 500V

<2,0mA - 50V, 100V, 250V, 1000V

Rated measuring current

2,17 mA - 500V/230k

1mA - 1000V/1M

If the instrument measures a voltage higher than 30V, the instrument will not take a
measurement.

Safety standards
Insulation:

Class 2, double insulation

Over voltage category:

CAT III

37