The filter and hvac store, Guide specifications, Flanders - foremost in air filtration – Honeywell 11255 User Manual

Page 42: Corporate headquarters, st. petersburg, fl

Advertising
background image

42

1.0 General

1.1 Medium efficiency UL Class 1 fire rated pleated

filters shall be Pre Pleat Class 1 as manufactured
by Flanders.

1.2 Filter sizes and capacities shall be scheduled on

the drawings.

2.0 Filter Construction

2.1 Filter media shall be manufactured of a high loft-

ed micro-fine media with a minimum efficiency of
50% per ASHRAE Standard 52.1

2.2

A corrosion-resistant expanded metal wire grid

shall be bonded to the media to maintain pleat
integrity.

2.3 The die-cut frame shall be flame-resistant, miner-

al-filled board to meet a UL Class 1 fire rating.

3.0 Performance

3.1 Initial and final resistance shall not exceed the

final values.

3.2 Media must meet or exceed the ratings that of the

specified filter.

3.3 The manufacturer shall guarantee performance

as stated in the literature within tolerances as
outlined in Section 7.4 of ARI Standard 850.

Guide Specifications

Resistance (Inches w

.g.)

0.25

0.75

0.50

1.00

1.50

1.25

0

Air Flow - CFM

0

1000

1500

2000

2500

Rate of Air Flow vs Initial Resistance

Arrestance vs. Dust Fed

Arrestance (%)

Dust Fed (grams)

100%

90%

80%

70%

60%

50%

40%

30%

20%

10%

0%

25 40 55 70 85 100

Efficiency vs. Dust Fed

Dust Fed (grams)

0 10 20 30 40 50 60 70 80 90 100

100%

90%

80%

70%

60%

50%

40%

30%

20%

10%

0%

Dust Spot Ef

ficiency

Resistance vs. Dust Fed

Resistance (Inches w

.g.)

Dust Fed (grams)

0 10 20 30 40 50 60 70 80 90 100

1.75

1.50

1.25

1.00

0.75

0.50

0.25

0.00

Flanders - Foremost in Air Filtration

Corporate Headquarters, St. Petersburg, FL

Performance values stated may be averages typical of the products listed.
Contact factory for actual performance test reports on specific products.

the filter and hvac store