General

Flanders offers a complete line of Alpha Cell HEPA
Filters in two efficiencies to meet the needs of criti-
cal applications where HEPA filtration is required.
Individual testing, rigid quality control and modern
assembly methods are used to ensure confor-
mance to specifications. Alpha Cell HEPA and
ULPA Filters are either UL 900 Class 1 or Class 2
listed.

Testing

Flanders individually tests and certifies each Alpha
Cell HEPA Filter to meet the customer’s require-
ments for resistance and efficiency (penetration) at
the filters nominal rated capacity. This information
appears on a test label affixed to the filter. When
used with correctly selected and installed mounting
frames or housings, Flanders Alpha Cell HEPA
Filters will easily pass an in-place validation test to
determine the overall system efficiency.

HEPA FILTERS

Each Alpha Cell HEPA Filter has a minimum effi-
ciency of 99.97% on 0.30 micrometer size particles
when tested at rated capacity on a Q-107
Penetrometer. Filters rated for 1000 cfm or less are
challenged with an approved nearly monodis-

persed oil aerosol of 0.30 micrometer size. Filters
rated for flows greater than 1000 cfm are tested
using a polydispersed oil aerosol. By measuring the
upstream and downstream concentration of these
particles with a light scattering photometer, the pen-
etration can be determined and the efficiency can
be calculated.

Scan Tested HEPA Filters

Each Scan Tested Alpha Cell HEPA filter has a min-
imum efficiency of 99.99% on 0.30 micrometer par-
ticles. Scan testing is in accordance with Section
6.2 of IEST-RP-CC034.1, HEPA and ULPA Filter
Leak Tests. In the scan test, the filter is challenged
with a high concentration of an approved oil aerosol
or PSL (Polystyrene Latex Spheres). The media
pack and pack-to-frame seal is scanned using a
photometer or particle counter to ensure that there
are no leaks greater than .01% of the upstream
concentration at 100 fpm face velocity.

Higher Efficiency ULPA Filters

Flanders can provide Pureform

®

and Separator

Style ULPA Filters with efficiencies up to 99.9995%
on 0.12 micrometer size particles. Please contact
the factory for more information.

Alpha Cell

HEPA Filters

See component chart on page 83.

Typical applications for
Alpha Cell Filters include:

• Hospitals

• Biomedical

• Pharmaceutical

• Biotechnology

• Genetic Research

• Universities

• Laboratories

• Food Processing

• Photo Processing

• Semiconductor Fabrication

• Industrial Processing Systems