The filter and hvac store, Guide specifications construction, Performance data capacities and dimensions – Honeywell 11255 User Manual

Page 76: Flanders - foremost in air filtration

Advertising
background image

76

Guide Specifications

Construction

Moisture separators are constructed much like permanent metal washable filters. The nominal two inch thick
media pack consists of 15 individual layers of pleated and flat aluminum wire mesh.

Air entering and exiting support grids are expanded metal, and the media enclosing frame is 16 ga. galva-
nized steel with five 3/8” diameter holes in the bottom for drainage.

Notes
1.Model MSG separators for use in side access housings with drain tube option are furnished with neoprene

gaskets on vertical sides to prevent moisture bypass.

2. Actual separator size is 5/8” under on both height and width. Actual depth is 1-7/8”
3. For maximum capture of liquid droplets, operate separators in the 500 fpm + 10% range.
4. Pd= Pressure Drop, in w.g.
5. Special sizes are available. Contact your local representative or the factory.
6. Performance values stated may be averages typical of the products listed. Contact factory for actual perform-

ance test reports on specific products.

1.0 General

1.1 Moisture separators shall be Models MS or MSG

as manufactured by Flanders.

1.2 Separator sizes and capacities shall be as

scheduled on the drawings.

2.0 Filter Construction

2.1 Enclosing frame shall be nominal 2” thick 16 ga.

galvanized steel with five 3/8” drain holes in the
bottom.

2.2 The media pack shall consist of 15 individual lay-

ers of pleated and flat aluminum wire mesh.

2.3 The face grids on the entry and exit sides shall be

expanded metal.

2.4 Arrow on top of frame shall indicate placement of

separator as to air flow and drainage position.

2.5 Model MSG separators for use in side access

housings with drain tube option shall have neo-
prene gaskets on vertical frame sides to prevent
liquid by-pass.

3.0 Performance

3.1 Separators shall have a minimum efficiency of

98% on 20 micrometer water or oil droplets when
operated at 500 fpm gross face velocity.

3.2 Initial resistance shall not exceed the scheduled

values.

4.0 Installation

4.1The installing contractor shall construct filter

banks or provide housings with drain tubes in
accordance with the separator manufacturer’s
recommendations.

4.2 Drain tubes and/or drain manifold shall be

trapped before running the piping to an open
drain.

Performance Data

Capacities and Dimensions

Model Number

Recommended Range of Face Velocities (FPM)

For Built-up

For Side Access

Nominal Size

Weight

Banks

Housings

HxWxD inches

375

450

500

550

625

Each

(Note 1)

(Note 2)

(lbs)

MS24242

MSG-24242

24x24x2

1500

.14

1800

.20

2000

.22

2200

.28

2500

.34

15

MS-12242

MSG-12242

12x24x2

750

.14

900

.20

1000

.22

1100

.28

1250

.34

9

MS-24122

MSG-24122

24x12x2

750

.14

900

.20

1000

.22

1100

.28

1250

.34

9

Flanders - Foremost in Air Filtration

Corporate Headquarters, St. Petersburg, FL

the filter and hvac store

Advertising