Guide Specifications

1.0 General

1.1 Minipleat HEPA/ULPA filters shall be Alpha Panel

Model AP493 or AP591 as manufactured by
Flanders.

1.2 Filter sizes and capacities shall be as scheduled

on the drawings.

1.3 Filter construction shall meet UL 900 Class 2

requirements.

2.0 Construction

2.1 The filter pack shall be 2.1” (53 mm) thick and

shall consist of moisture-resistant microfine fiber-
glass co taining a water-repellant binder.

The

media shall be formed into closely spaced pleats
and stabilized with polyurethane bead separa-
tors.

2.2 The filter pack shall be urethane sealed in a

clearcoat-anodized extruded aluminum frame
3”deep.

2.3 Extruded aluminum media dividers shall be pro-

vided on filters over 36” wide and 24” in height.

2.4 Furnish 0.25” thick x 0.75” wide closed cell

neoprene gaskets on the face flanges when
required.

3.0 Performance

3.1 Particle size efficiency shall be certified to be not

less than 99.99% on 0.30 micron or 99.99% on
0.12 micron. Each filter is scan tested with auto-
mated laser equipment.

Filters shall meet the

requirements of IEST RP-1 for Type C or F filters.

3.2 Initial resistance shall not exceed the scheduled

values.

3.3 Filters shall be capable of operating up to 150 fpm

face velocity.

Drawing Notes:

1. Physical Data

Media: Moisture-resistant fiberglass
Filter Construction: 2.1” (53 mm) thick separatorless

minipleat

Filter Frame: Clearcoat-anodized extruded aluminum
Media Divider: Extruded aluminum channel

2. Add 0.25” to the 3” depth for each gasket.
3. Media dividers are furnished on air filters over 36” in

width. Filters over 24” in height are also furnished
with media dividers and media pleats that are paral-
lel to the width.

Performance Data Notes:

1. Filters are scan-tested for leaks after assembly and

are certified to be 99.99% on 0.30 Fm or 99.99% on
.012 Fm particles.Performance meets the require-
ments of IEST RP-1 for Type C or F filters.

2. Dimensional tolerances are +0” -.13”on height and

width, + 0.6” on depth and +.13” on diagonal dimen-
sions.

3. Maximum operating conditions: 200 degrees F, 100%

RH.

4. Filters are designed to UL 900 Class 2 requirements.
5. Gasket location: Suffix D denotes a downstream gas-

ket. Use suffix U for upstream, B for both upstream
and downstream gasketing and N if no gaskets are
required.

Performance Data - Capacities and Dimensions

Particle

Size

Efficiency

99.99% on

0.30 Fm

H

W

70

90

110

Cfm Capacity at

Gross Face Velocity,

fpm

99.99% on

0.12 Fm

AP493-2424*

AP493-2448*

AP591-2424*

AP591-2448*

Clean Filter Resistance (inch

24

24

24

48

24

24

24

48

Model Number

280

560

.35

280

560

.50

360

720

.45

360

720

.65

440

880

.55

440

880

.80

Actual

Dimensions

(inch)

Clean Filter Resistance (inch

H

W

3” depth,

.75” Flange (typical)

*Insert gasket designator: D, U, B or N. See Note 5.