The filter and hvac store – Honeywell 11255 User Manual

Page 89

Advertising
background image

89

Frame Materials

Alpha 2000 Filters are available in a variety of wood and metal frame materials such as particle board, ply-
wood, galvanized steel and stainless steel.

Gasket and Fluid Seal

The standard gasket seal is 0.75” x 0.25” neoprene for installation on either the upstream, downstream or
both sides of the filter. The standard Fluid Seal is Flanders Blu-Jel® Seal which is a two - part silicone mate-
rial suitable for temperatures up to 390°F.

Faceguards (Optional)

Faceguards are used to protect the filter media from mechanical damage. The typical faceguard material is
expanded aluminized steel. Galvanized 4 x 4 mesh welded wire and Type 304 stainless steel are also avail-
able.

UL Listings

Alpha 2000 Filters are either UL900 Class 1 or Class 2 listed depending on materials of construction.

Holding Frames and Housings

Alpha Frames are designed for Alpha 2000 filters in built-up filter banks. Each filter is secured in the frame
with four bolt-type fasteners that either compress the gasket or press the knife edge into the gel in the filter
channel to maintain a leak-tight seal.

Surelock HEPA Filter Housings are recommended for side-access applications. The filters are sealed in
place with either spring-loaded swing arm assemblies or a locking mechanism. The swing arm assemblies
or locking mechanism either compress the gasket or press the knife edge into the gel in the filter channel
to maintain a leak-tight seal.

Gasket
Seal

Frame or
Housing

Blu-Jel
Seal

Filter

Knife Edge
On Frame or
Housing

Fluid
Seal
Channel
On Filter

Frame or
Housing

Surelock HEPA Housing

Alpha Frame, B1 Frame, A-4 Frame

Flanders - Foremost in Air Filtration

Corporate Headquarters, St. Petersburg, FL

the filter and hvac store

Advertising