The filter and hvac store, Guide specifications – Honeywell 11255 User Manual

Page 98

Advertising
background image

Clean Filter Resistance(“w.g)

Clean Filter Filter Resistance(inchw.g)

23-5/8
47-5/8

PF†-493-2424-*
PF†-493-2448-*

PF†-591-2424-*
PF†-591-2448-*

23-5/8
47-5/8

Physical Data Notes:

1. *Insert suffix 10 (nominal 10”collar) or 12 (nominal 12” collar).

Add “G” to suffix to designate the insulation option.

2. Tolerances: L and W: +0, -1/8” D: + - 1/8”

3. Maximum operating conditions: 200 ° F, 100%RH

4. Modules are designed to UL 900 Class 2 requirements.

5. Installed weight:

PF53P

F70P

F100

2424:

20lbs.

25lbs.

27lbs.

2448:

35lbs.

40lbs.

43lbs.

6. D = 5 3/4” (PF 53)

D = 7 3/4” (PF 70, PF 100)
H = D + 2”

1.0 General

1.1 Terminal filter HEPA/ULPA Modules shall be

Pureflo Model PF as manufactured by Flanders
and shall be scan tested for leaks after assem-
bly.

1.2 Module sizes, filter pack depth, efficiencies and

capacities shall be as scheduled on the draw-
ings.

2.0 Module Construction

2.1 The module filter pack shall be constructed of

water-laid microfine fiberglass media containing
a water-repellent binder.

The media shall be

formed into closely - spaced pleats held in posi-
tion by adhesive bead separators.

2.2 The filter pack shall be polyurethane-sealed into

a clear coat - anodized extruded aluminum
frame and

rectangular tube section center

divider.

2.3 Module top/inlet collar shall be one-piece alu-

minum.

2.4 The protective face grille shall be 20 ga. expand-

ed steel finished in white powder coat paint.

2.5 Provide an airflow damper adjustable from the

room side and accessible through a port with a
removable plug located in the center divider.

2.6 Provide a separate port in the center divider that

is open to the inlet side of the filter for measure-
ment of static pressure and challenge aerosol
concentration. The port shall be fitted with a
removable plug.

3.0 Performance

3.1 Initial and final resistances shall not exceed the

scheduled values.

3.2 The airflow damper shall be capable of regulat-

ing the module face velocity from 70 fpm to 110
fpm.

3.3 Performance shall meet the requirements of

IEST RP - 1 for Type C or F filters.

Guide Specifications

Model Number

Particle

Size

Efficiency

%

99.99 on

0.30 µm

99.9995 on

0.12 µm

Cfm Capacity at Gross Face Velocity, Fpm

PF53

PF70

PF100

70

280
560

.40

280
560

.55

90

360
720

.50

360
720

.70

110

440
880

.60

440
880

.85

70

280
560

.33

280
560

.45

90

360
720

.42

360
720

.58

110

440
880

.50

440
880

.70

70

280
560

.23

280
560

.33

90

360
720

.30

360
720

.42

110

440
880

.37

440
880

.50

Actual Length

L (inches)

† Insert filter pack depth in mm: 53, 70, or 100

the filter and hvac store

Advertising