Nominal Size

250 FPM

375 FPM

500 FPM

625 FPM

750 FPM

Media

Wt.

Efficiency

Model

HxWxD

Area

Each

%

Number

Inches

(Sq.Ft) (Lbs.)

CFM

PD

CFM

PD

CFM

PD

CFM

PD

CFM

PD

Guide Specifications

Performance Data Notes:

1. PD represents clean pressure drop in inches w.g.

The recommended final pressure drop for all models
is 2.0 inch w.g. Maximum final pressure drop is 3.2
inch w.g.

2. Operation down to zero air flow is satisfactory for all

models

3. Efficiency is average and is based on ASHRAE

Standard 52.1 test methods for 65, 85, 95 and 98%
filters. Performance values stated may be averages
typical of the products listed. Contact factory for actual
performance test reports on specific products.

4. Performance tolerances conform to section 7.4 of

ARI Standard 850.

5. Actual filter header is 5/16 inch under on height an

width. Actual depth is 11-1/2 inch

Installation Considerations

Superflow-V filters may be installed in Flanders Type 9

Holding Frames, K-Trac Filter Framing Modules,
Sureseal Side Access Housings or in similar existing
hardware. Type 9 Holding Frames are riveted
together to form a filter bank. K-Track Filter
Framing Modules are especially suitable for medium
to large built-up filter banks. Smaller systems and
systems with minimum upstream access space are
best served using Sureseal Side Access Housings.

Gasketed Headers are Standard
Superflow-V filters are furnished with a peripheral head-

er on the air entering side and with foam gaskets on
the “H” dimension for the 24 x 24 model and “W”
dimension on the 12 x 24 and 20 x 24 models.

1.0 General

1.1 Medium and high efficiency extended surface low

pressure drop minipleat filters shall be Superflow-
V models as manufactured by Flanders.

1.2 Filter sizes, efficiencies and capacities shall be as

scheduled on the drawings.

2.0 Filter Construction

2.1 Filters shall consist of multiple minipleat panels

bonded to flame-retardant plastic panels on top
and bottom and encased in a corrosion-resistant
steel frame.

3.0 Performance

3.1 Initial and final resistances shall not exceed the

scheduled values.

3.2 Media area must equal or exceed that of the spec-

ified filter.

3.3 The average efficiency shall be as determined by

ASHRAE Standard 52.1 test methods.

3.4 Filters shall be UL 900 Class 2 listed.

95% DOP

SFVD-95A12

24 x 24 x 12

1000

0.28

1500

0.55 2000 0.75

2500 0.80

*

*

196

18

95% DOP

SFVD-95B12

20 x 24 x 12

800

0.28

1200

0.55 1600 0.75

2000 0.80

*

*

162

14

95% DOP

SFVD-95C12

12 x 24 x 12

500

0.28

750

0.55 1000 0.75

1250 0.80

*

*

98

9

98%

SFV-98A12

24 x 24 x 12

1000

0.25

1500

0.45 2000 0.60

2500

1.0

*

*

196

17

98%

SFV-98B12

20 x 24 x 12

800

0.25

1200

0.45 1600 0.60

2000

1.0

*

*

162

13

98%

SFV-98C12

12 x 24 x 12

500

0.25

750

0.45 1000 0.60

1250

1.0

*

*

98

8

95%

SFV-95A12

24 x 24 x 12

1000

0.14

1500

0.27 2000 0.36

2500 0.51

3000 0.64

196

17

95%

SFV-95B12

20 x 24 x 12

800

0.14

1200

0.27 1600 0.36

2000 0.51

2400 0.64

162

13

95%

SFV-95C12

12 x 24 x 12

500

0.14

750

0.27 1000 0.36

1250 0.51

1500 0.64

98

8

85%

SFV-85A12

24 x 24 x 12

1000

0.07

1500

0.18 2000 0.27

2500 0.40

3000

0.6

196

17

85%

SFV-85B12

20 x 24 x 12

800

0.07

1200

0.18 1600 0.27

2000 0.40

2400

0.6

162

13

85%

SFV-85C12

12 x 24 x 12

500

0.07

750

0.18 1000 0.27

1250 0.40

1500

0.6

98

8

65%

SFV-65A12

24 x 24 x 12

1000

0.05

1500

0.15 2000 0.25

2500 0.38

3000 0.52

196

17

65%

SFV-65B12

20 x 24 x 12

800

0.05

1200

0.15 1600 0.25

2000 0.38

2400 0.52

162

13

65%

SFV-65C12

12 x 24 x12

500

0.05

750

0.15 1000 0.25

1250 0.38

1500 0.52

98

8

the filter and hvac store